EAOM-210 FLJ.eng / ver 0.0
Pages 77 / 132
CONFIGURABLE OUTPUTS SELECTIONS
0 NOT USED
Output is not used
1 AUDIBLE ALARM
The output indicates that the internal sounder is operating. It may be use for external
sounder.
2 ALARM RESET
The output indicates that an alarm reset being performed. Once the alarm reset has been
completed, the output become inactive again. The output could be used to give an external
reset signal to external systems.
3 AUTO START INHIBIT
This output indicates that a digital input that has been configured as ‘auto start inhibit’ is
active.
4 AUXILIARY MAINS FAILURE
This output indicates that a digital input that has been configured as ‘auxiliary mains failure’
is active.
5 BATTERY HIGH VOLTAGE
This output indicates that a battery high voltage alarm has occurred.
6 BATTERY LOW VOLTAGE
This output indicates that a battery low voltage alarm has occurred.
7 CALLING FOR SCHEDULED RUN
This output indicates that a scheduled run has been called for. If the module is in the ‘auto’
and mains okey, the module will change mode to ‘test’ and the generator will run if no
shutdown alarms are present.
8 CHARGE ALTERNATOR FAILURE
This output indicates that a charging alternator failure has occurred
9 COMMON ALARM
This output indicates that a warning, electrical trip or shutdown alarm has been activated.
10 COMMON ELECTRICAL TRIP ALARM
This output indicates that an electrical trip alarm has been activated. This output can only be
reset by removal of the fault and by then pressing the RESET button.
11 COMMON SHUTDOWN ALARM
This output indicates that a shutdown alarm has been activated. This output can only be
reset by removal of the fault and by then pressing the RESET button or by using an external
‘alarm reset’ input.
12 COMMON WARNING ALARM
This output indicates that a warning alarm has been activated. This output is normally self-
resetting on removal of the fault.