EAOM-210 FLJ.eng / ver 0.0
Pages 33 / 132
3.4.1 Changing and Saving Technician Parameter Values
Example-1 : To change CT Primary parameter in ”GENERATOR CURRENT/POWER ACTIONS
PAGE”, user must access to “GEN.CUR/PW.ACT.PAGE” firstly.
TECHNICIAN SECTION
PROG
When the prog button is
pressed, password is
asked for accessing to
parameters.
PROG
OPERATOR SECTION
PROG
TECHNICIAN PASSWORD
Press the Enter button to
confirm password. If the
password is incorrect, the
unit will drop out of
program mode.
TECHNICIAN SECTION
PASSWORD
162
PROG
User can access to technician parameters
by entering technician password. This
selection is done with increment and
decrement buttons.
Press the Enter button.
TECHNICIAN SECTION
PASSWORD
0
PROG
Enter password with
increment and
decrement buttons.
Note1:
If Enter button is pressed
and the technician password is
zero, Password screen is ignored.
TECHNICIAN SECTION
GEN.CUR/POW.ACT.PAGE
PROG
GENERATOR CURRENT/POWER
ACTIONS Page
Operator can not
access to this page.
TECHNICIAN SECTION
GEN.CUR/POW.ACT.PAGE
CT PRIMARY
Vac
100
PROG
Press Enter button to access to
first parameter in Generator
Current/Power Actions page.
Parameter can be changed with
increment and decrement buttons
Press Enter button to confirm the
changed value and access to the
following parameter.
CT Primary parameter
TECHNICIAN SECTION
GEN.CUR/POW.ACT.PAGE
CT PRIMARY
Vac
500
PROG
Operation Screen
MAINS & LOAD
L12: 380Vac I1: 126A
Fq:50.0Hz
AUTO
L23: 380Vac I2: 126A
L31: 380Vac I3: 126A
IT: 378A
IEA: 63A
CRANKNG ATTEMP
OVER SPEED PREALARM!