AC SYSTEM 3 PHASE 4 WIRE OR 1 PHASE 2 WIRE
0: AC system is 1 phase 2 wire.
1: AC system is 3 phase 4 wire.
2: AC system is 3 phase 4 wire series delta.
3: AC system is 1 phase 3 wire.
FAST LOADING FEATURE EN/DIS
ENABLE: The module will terminate the safety on timer once all monitored parameters have
reached their normal settings. This feature is useful if the module is to be used as a standby
controller as it allows the generator to start and go on load in the shortest possible time.
DISABLE: Normal operation, the safety on timer will be observed in full. This feature is useful
if the module is to be used with some small engines where pre-mature termination of the
delay timer can lead to over speed alarms on start up.
ALL WARNINGS ARE LATCHED EN/DIS
Disable: Normal operation, the warnings and pre-alarms (except spare inputs, because they
have their latching or non-latching selections) will automatically reset once the triggering
condition has cleared.
Enable: Warnings and pre-alarms will latched when triggered. To reset the alarm either an
external reset must be applied to one of the inputs or the ‘Reset’ pushbutton operated, once
the triggering condition has cleared.
MAINS FAILURE DETECTION EN/DIS
Disable: The module will not monitor the AC mains supply for failure. The AC mains
instrumentation will still be active however.
Enable: The module will monitor the incoming AC mains supply. Should the supply go out
side of limits the module will initiate its automatic mains failure sequence.
LOOK MAINS FAILURE FOR MAINS CONTACTOR EN/DIS
Disable: In the event of a mains failure the EAOM-210 FLJ will attempt to maintain the supply
to the load for the incoming AC mains supply until the generator is available to go on load. In
the event of a generator failure the module will default back to the incoming AC mains
supply. This provides a ‘fail-safe system’, ensuring that in the event of a system failure the
load will still be fed from the AC mains supply.
Enable: As soon as the module detects a mains failure the mains contactor or breaker relay
will be opened to remove the supply from the load. This is to prevent damage to the load in
case of single-phase failure, especially useful if the load is a 3-phase motor or pump. The
supply to the load will then be fed from the gen-set once it is available. In the event of
generator failure the module will open the generator relay and remove the supply to the load
until either the mains supply is restored or the generator is restarted.
ENGINE FUEL (DIESEL /GAS) SELECTION
Diesel or Gas engine can be selected.
If diesel engine selected:
STOP/FUEL SELECTION
Selection for the engine has Fuel or Stop solenoid.
STOP SOLEONID TIME
This timer is used if the unit is configured to operate an Energise to stop engine. It dictates
the duration that the Stop Solenoid output will remain active after the module has detected
the engine has come to rest. If the Stop Solenoid output is not configured, this timer will still
operate, preventing an immediate restart.