If this parameter is selected as “Disable”, The ECU remote control via the J1939 protocol will
be disabled.
RESET PREVIOUSLY ACTIVE DTCs – DM3
If this parameter is selected as “Yes”, a DM3 message "Acknowledge passive faults" is
sent. After this parameter is reset automatically to “No”.
SPEED CONTROL via J1939
If this parameter is selected as “Enable”,
The speed sensing from J1939 ECU will be used for
the speed (Rpm) failures.
OIL PRESSURE CONTROL via J1939
If this parameter is selected as “Enable”,
The oil pressure sensing from J1939 ECU will be
used for the oil pressure failures and the engine started signal.
COOLANT TEMPERATURE CONTROL via J1939
If this parameter is selected as “Enable”,
The coolant temperature sensing from J1939 ECU
will be used for the coolant temperature failures.
(CAN ERROR SET PAGE) CAN BUS & J19139 ERROR ACTIONS page
CAN FAULT ACTIONS
Can Fault Actions:
0- Disable
1- Warning Non-Latching
2- Warning (Alarm Only, No Shutdown)
3- Electrical Trip (Alarm/Off Load
Generator Followed By Shutdown After
Cooling)
4- Shutdown (Alarm And Shutdown)
(dis)0-4
dis
CAN FAULT ACTIV.
Can Fault Activation:
0- Active From Starting
1- Active From Safety On
2- Always Active
0 – 2
2
CAN FAULT DELAY
Can Fault Delay
Sec
2 - 250
10
AMBER WARN ACTIONS
J1939 Amber Warning Lamp Actions:
0- Disable
1- Warning Non-Latching
2- Warning (Alarm Only, No Shutdown)
3- Electrical Trip (Alarm/Off Load
Generator Followed By Shutdown After
Cooling)
4- Shutdown (Alarm And Shutdown)
(dis)0-4
dis
AMBER WARN ACTIV.
J1939 Amber Warning Lamp Activation:
0- Active From Starting
1- Active From Safety On
2- Always Active
0 – 2
2
AMBER WARN DELAY
J1939 Amber Warning Lamp Delay
Sec
0 - 250
2
RED STOP ACTIONS
J1939 Red Stop Lamp Actions:
0- Disable
1- Warning Non-Latching
2- Warning (Alarm Only, No Shutdown)
3- Electrical Trip (Alarm/Off Load
Generator Followed By Shutdown After
Cooling)
4- Shutdown (Alarm And Shutdown)
(dis)0-4
dis
RED STOP ACTIVATION
J1939 Red Stop Lamp Activation:
0- Active From Starting
1- Active From Safety On
2- Always Active
0 – 2
2
RED STOP DELAY
J1939 Red Stop Lamp Delay
Sec
0 - 250
2