background image

[email protected]

ENVIROMASTER INTERNATIONAL LLC

4

SECTION THROUGH FASCIA

FASCIA BLANKING PIECE

3. Condensate pipework should slope downwards in the

direction of water flow with a minimum gradient of (1” per
10’). There must not be any uphill gradients other than
in the first 18” of pipework from the Cassette.

4. When multiple Cassettes are connected to a common

condensate drain, ensure the drain is large enough to
cope with the volume of condensate from several
Cassettes. It is also recommended to have an air vent in
the condensate pipework to prevent any air locks.

DUCT COLLARS:

 Branch duct and fresh air duct collars

can be attached to the Cassette chassis by following the
steps below:

1. Refer to the relevant illustration for your Cassette 

(pages

6 -7 in this IOM)

 to become familiarized with knock-out

hole locations.

2. The insulation is pre-cut to aid location and removal of

the relevant section. Rub hand across surface of
insulation to reveal exact location of knock-out.

3. Remove the metal knockout from the chassis.

4. Attach the duct collar to the chassis using self tapping

screws.

NOTE: Branch ducts are round and 5 - 6” in diameter.
Fresh Air ducts are square and  3” in diameter.

INSULATION:

 Refrigerant, chilled water and condensate

pipes should be insulated right up to the Cassette chassis.
Chilled water valves must also be insulated to prevent sweat-
ing.

ASSEMBLY:

 Once the services have been connected the

four fascia mounting bolts can be unscrewed approximately
1” from the condensate tray support channels.

The fascia can now be unpacked ready for fitting to the Cas-
sette chassis. Ensure the black fir tree fasteners holding
the fascia polystyrene are pushed in firmly in case of transit
vibration. If a fascia aperture needs blanking off, then take
one of the polystyrene blanking pieces and push it into the
recess in the polystyrene fascia insulation. Fit by removing
the inlet grilles and filters, locating the four fascia mounting
bolts on the chassis through the four keyhole brackets on
the fascia and then sliding the fascia sideways until it locks
into position.

NOTE: Up to two non-adjacent sides can be blanked
off.

NOTE:

 

On electro-mechanical units, the fascia must

be installed with the EMI logo along the same edge of
the unit as the electrical panel. On units fitted with
microprocessor controls, orient the fascia with the dis-
play panel along the same edge of the unit as the
electrical panel.

Before tightening the fascia to the unit, connect the two halves
of the vane motor’s plug and socket connection (where ap-
plicable).

On microprocessor controlled units, ensure that the display
panel cable is routed to the electrical panel and securely
fastened to its connector on the microprocessor circuit board.
(Refer to the unit’s electrical wiring schematic).  Take care
to ensure that the connector is connected in the proper ori-
entation and that the wires are not routed such that they
may become trapped, cut, broken or chaffed.

The fascia can now be tightened up to the Cassette chassis
until a good seal is obtained between fascia and chassis.

NOTE: Do not over tighten the bolts.  To do so may
cause damage to the fascia.

With filters in place, the inlet grilles can now be fitted to the
fascia to complete the installation.

ELECTRICAL DATA

(See Appendix 1 on page 18 for wiring charts and instruc-
tions.)

All power and interconnecting wiring between units should
be carried out to conform with local/national electrical codes.
A fused and dedicated electrical supply of the appropriate
phase, frequency and voltage should be installed by the cus-
tomer. It is also recommended that a local disconnect switch
be connected within 3’ of the unit. In some areas this may
be a code requirement.

EMI equipment in its standard form is designed for an elec-
trical supply of 208-230V, 1Ph, 60Hz. When connection to a
115V, 1Ph, 60Hz  supply is necessary, a factory mounted
buck boost transformer will be fitted to the unit.

The wires should be capable of carrying the maximum load
current under non-fault conditions at the stipulated voltages.
Avoid large voltage drops on cable runs, particularly in low
voltage wiring. The correct cable size must be used to en-
sure a voltage drop of less than 1 volt in the control wiring.
Once the refrigeration pipe work is complete, the electrical
supply can be connected by routing the cable through the
appropriate casing hole and connecting the supply and ground
cables to the unit’s power terminals. On the medium and
large cabinets, it will be necessary to remove the insulated
condensate tray support rail, adjacent to the casing hole.

Содержание WLCA

Страница 1: ...ions CAF4 in 8 000 to 36 000 Btuh capacities and depending on the model elec tric heat can also be factory fitted as an option Designed for low noise levels easy installation and maintenance and a sli...

Страница 2: ...the fresh air knockouts on the Cassette case It is usually advised that the fresh air volume is approximately 10 of the unit s pub lished maximum air flow SITE INSTALLATION UNPACKING The cassette fas...

Страница 3: ...by folding the metal bracket by hand along the row of holes The Cassette can now be lifted onto the hanging rods and leveled at the correct distance from the ceiling with the aid of the installation g...

Страница 4: ...installed with the EMI logo along the same edge of the unit as the electrical panel On units fitted with microprocessor controls orient the fascia with the dis play panel along the same edge of the u...

Страница 5: ...ssette and interconnecting pipework with dry nitrogen to a pressure of 150 PSIG Record the pressure over a pe riod of time a minimum period of 60 minutes should be suf ficient to detect any major leak...

Страница 6: ...RELEVANT OUTDOOR UNIT MANUAL AND IN ADDITION NOTE THE FOLLOWING 1 0 PRE START UP CHECKLIST 2 2 ON OFF WORKS 2 3 INDOOR UNIT THREE FANS SPEEDS AVAILABLE MICRO ONLY 2 4 VANE SWEEP FUNCTIONS 2 5 TIMER F...

Страница 7: ...4 SUCTION AT EM I CONDENSER 7 8 SUCTION AT EM I CONDENSER WIRE FRAMED PERIFRAME CAF 4 TECHNICAL DATA CABINET DIMENSIONS 8 12 18 20 33 36 HEIGHT 10 3 4 9 1 2 9 1 2 9 1 2 11 1 2 11 1 2 WIDTH 22 1 2 32...

Страница 8: ...EMI ENVIROMASTER COM ENVIROMASTERINTERNATIONALLLC 8 SMALL CABINET CAH 9 000 12 000 CAHW 9 000 ONLY CAF 8 000 12 000 CAF4 8 000 ONLY EMI CASSETTE DIMENSIONS...

Страница 9: ...000 24 000 CAHW 12 000 24 000 CAF 18 000 20 000 CAF4 12 000 20 000 CASSETTE DIMENSIONS INCHES SIZE A B C D E F G H J K L M N MEDIUM 11 37 37 1 32 32 2 5 3 9 33 LARGE 13 49 37 1 32 45 2 6 13 9 45 EMI...

Страница 10: ...connected by a 7 pin plug and socket The green On Off indicator will remain lit when the unit is running or will flash if heating or cooling is required but the compressor anti cycle timer is delayin...

Страница 11: ...ir vanes to oscillate when selected not applicable to all models OFF Switches the unit off in certain instances the fan may be subject to a 2 minute run on time to dissipate residual heat ON SEND Pres...

Страница 12: ...riday 1 Press CLK Timer twice Program highlights NOTE Display will stop flashing after 15 seconds 2 Select Program 1 by pressing or Program 1 and Start Time will flash 3 Press or to select and change...

Страница 13: ...from the unit by opening the 1 4 air bleed Re tighten the bleed screw once all air has been re moved 8 Repeat steps 1 4 above for all Cassettes in the same systems The Cassettes are now ready for the...

Страница 14: ...MUM PUMP LIFT EXCEEDED Check that the con densate pump head is no greater than 18 See installation section of this manual for more information BLOCKED KINKED CONDENSATE PIPE See section Wa ter Leaking...

Страница 15: ...perating pressures Check filter condition See maintenance instruc tions for more information CONDENSATE PUMP BLOCKED OR FAILED See sec tion Water Leaking From Unit COIL FREEZE UP Acoil freeze conditio...

Страница 16: ...TOR Check actuator by manu ally opening and closing valve replace if faulty FAULTY HEATER RELAY Check signals to relay and check action of relay contacts Replace relay or PCB if nec essary FANS WILL N...

Страница 17: ...al condensate tray support channels and pull the channels away from the condensate tray Pull thecondensatetraydownwardsawayfromthechas sis 3 Remove the electrical panel lid and disconnect the fan conn...

Страница 18: ...equired 1 Insert the screwdriver into the square hole until you hit bottom This will open the terminal block so that it will accept your wire s 2 Insert the stripped wire into the oval or round hole 3...

Страница 19: ...anes 4 14 Freeze Protection Thermostat DX Electro Mechanical Version only 15 Filter 16 Fascia Assembly 17 Receiver Microprocessor Version 18 Terminal Rail Relays Timer Micro Electro Mechanical Version...

Страница 20: ...2 Vane Motor Assembly 13 Filter 14 Fascia 15 Remote Handset 16 Control Box Lid 17 Control Box PCB 18 Control Box 19 Coil Bracket 20 Expansion Valve Enviromaster International LLC 5780 Success Drive Ro...

Отзывы: