background image

[email protected]

ENVIROMASTER INTERNATIONAL LLC

17

MAINTENANCE

EVERY 3 MONTHS:

 Check the air filter condition and clean

if necessary (see below).

EVERY 6 MONTHS:

 Same as 3 months plus clean conden-

sate tray with biocide suitable for polystyrene and clean fas-
cia.

EVERY 12 MONTHS:

 Same as 6 months plus check all

electrical connections for security, check condensate pump
operation, and check the heating and cooling action to en-
sure proper operation.

FILTER REMOVAL AND CLEANING

1. Ensure the unit is isolated from the electrical sup-

ply and ensure that the fan(s) has come to a com-
plete stop.

2. Unclip the catches along the edge of each grille

and allow them to hang from the fascia by the
molded plastic hinges located along the opposite
edge.

3. If desired, the grilles can be removed from the fas-

cia completely.

4. The filter can now be easily slid out of the small

plastic retaining clips on the back of each grille.

5. Gently vacuum clean the filters on a medium power

vacuum.

6. Replace filters by reversing steps 2 to 4.

NOTE:

 EMI recommends you keep at least one full

set of cassette air filters as spares.

FAN REMOVAL

CAUTION: Isolate from the electrical supply before
commencing work!!

1. Unclip the grille catches and remove the grille(s)

from the fascia.

2. For medium and large-sized units, remove the M6

screws from the black plastic inlet ring and pull the
inlet ring downwards from the condensate tray. For
small units only, remove the fascia by loosening
the four fascia mounting bolts and then slide the
fascia horizontally until it releases from the chas-
sis. Drain the condensate tray by removing the
small black rubber drain plug, catching the con-
densate (if any) in a suitable container. Remove
the self tapping screws securing the two insulated
metal condensate tray support channels and pull
the channels away from the condensate tray. Pull
the condensate tray downwards away from the chas-
sis.

3. Remove the electrical panel lid and disconnect the

fan connections from within the electrical panel.

4. Rotate the fan by hand until two M6 nuts are visible

through the fan mounting access holes. Remove
the two nuts.

5. Rotate the fan 90° until the remaining two nuts are

visible and remove while supporting the fan to pre-
vent it from falling. The fan can now be dropped
down from the unit.

CONDENSATE TRAY REMOVAL

1. Unclip the grille catches and remove the grille(s)

from the fascia.

2. Remove the fascia by loosening the fascia mount-

ing bolts and sliding the fascia horizontally until it
releases from the chassis. 

If unit is micropro-

cessor controlled, remove display panel cable
from within the electrical panel before remov-
ing the fascia.

3. Remove electrical panel lid by unscrewing the single

self tapper and pull the lid horizontally away from
the control box.

4. On medium and large sized units, disconnect the

main wiring from the incoming terminal block and
disconnect the fan wires from their connection points
within the electrical panel. Separate any two part
connectors coming from the electrical panel.

5. Drain the condensate tray by removing the small

black rubber drain plug, catching any condensate
in a suitable container.

6. Remove the self tapping screws securing the two

insulated metal condensate tray support channels
and pull the channels away from the condensate
tray. Pull the condensate tray, complete with inlet
ring (on medium and large sized units only) down-
wards away from chassis.

CONDENSATE PUMP REMOVAL

1. Disconnect condensate pump and float switch wires

from inside electrical panel.

2. Unscrew the three M4 screws holding the pump

inspection plate in place and pull the pump and
mounting bracket away from the chassis while feed-
ing the pump wires between condensate tray and
insulation.

Содержание WLCA

Страница 1: ...ions CAF4 in 8 000 to 36 000 Btuh capacities and depending on the model elec tric heat can also be factory fitted as an option Designed for low noise levels easy installation and maintenance and a sli...

Страница 2: ...the fresh air knockouts on the Cassette case It is usually advised that the fresh air volume is approximately 10 of the unit s pub lished maximum air flow SITE INSTALLATION UNPACKING The cassette fas...

Страница 3: ...by folding the metal bracket by hand along the row of holes The Cassette can now be lifted onto the hanging rods and leveled at the correct distance from the ceiling with the aid of the installation g...

Страница 4: ...installed with the EMI logo along the same edge of the unit as the electrical panel On units fitted with microprocessor controls orient the fascia with the dis play panel along the same edge of the u...

Страница 5: ...ssette and interconnecting pipework with dry nitrogen to a pressure of 150 PSIG Record the pressure over a pe riod of time a minimum period of 60 minutes should be suf ficient to detect any major leak...

Страница 6: ...RELEVANT OUTDOOR UNIT MANUAL AND IN ADDITION NOTE THE FOLLOWING 1 0 PRE START UP CHECKLIST 2 2 ON OFF WORKS 2 3 INDOOR UNIT THREE FANS SPEEDS AVAILABLE MICRO ONLY 2 4 VANE SWEEP FUNCTIONS 2 5 TIMER F...

Страница 7: ...4 SUCTION AT EM I CONDENSER 7 8 SUCTION AT EM I CONDENSER WIRE FRAMED PERIFRAME CAF 4 TECHNICAL DATA CABINET DIMENSIONS 8 12 18 20 33 36 HEIGHT 10 3 4 9 1 2 9 1 2 9 1 2 11 1 2 11 1 2 WIDTH 22 1 2 32...

Страница 8: ...EMI ENVIROMASTER COM ENVIROMASTERINTERNATIONALLLC 8 SMALL CABINET CAH 9 000 12 000 CAHW 9 000 ONLY CAF 8 000 12 000 CAF4 8 000 ONLY EMI CASSETTE DIMENSIONS...

Страница 9: ...000 24 000 CAHW 12 000 24 000 CAF 18 000 20 000 CAF4 12 000 20 000 CASSETTE DIMENSIONS INCHES SIZE A B C D E F G H J K L M N MEDIUM 11 37 37 1 32 32 2 5 3 9 33 LARGE 13 49 37 1 32 45 2 6 13 9 45 EMI...

Страница 10: ...connected by a 7 pin plug and socket The green On Off indicator will remain lit when the unit is running or will flash if heating or cooling is required but the compressor anti cycle timer is delayin...

Страница 11: ...ir vanes to oscillate when selected not applicable to all models OFF Switches the unit off in certain instances the fan may be subject to a 2 minute run on time to dissipate residual heat ON SEND Pres...

Страница 12: ...riday 1 Press CLK Timer twice Program highlights NOTE Display will stop flashing after 15 seconds 2 Select Program 1 by pressing or Program 1 and Start Time will flash 3 Press or to select and change...

Страница 13: ...from the unit by opening the 1 4 air bleed Re tighten the bleed screw once all air has been re moved 8 Repeat steps 1 4 above for all Cassettes in the same systems The Cassettes are now ready for the...

Страница 14: ...MUM PUMP LIFT EXCEEDED Check that the con densate pump head is no greater than 18 See installation section of this manual for more information BLOCKED KINKED CONDENSATE PIPE See section Wa ter Leaking...

Страница 15: ...perating pressures Check filter condition See maintenance instruc tions for more information CONDENSATE PUMP BLOCKED OR FAILED See sec tion Water Leaking From Unit COIL FREEZE UP Acoil freeze conditio...

Страница 16: ...TOR Check actuator by manu ally opening and closing valve replace if faulty FAULTY HEATER RELAY Check signals to relay and check action of relay contacts Replace relay or PCB if nec essary FANS WILL N...

Страница 17: ...al condensate tray support channels and pull the channels away from the condensate tray Pull thecondensatetraydownwardsawayfromthechas sis 3 Remove the electrical panel lid and disconnect the fan conn...

Страница 18: ...equired 1 Insert the screwdriver into the square hole until you hit bottom This will open the terminal block so that it will accept your wire s 2 Insert the stripped wire into the oval or round hole 3...

Страница 19: ...anes 4 14 Freeze Protection Thermostat DX Electro Mechanical Version only 15 Filter 16 Fascia Assembly 17 Receiver Microprocessor Version 18 Terminal Rail Relays Timer Micro Electro Mechanical Version...

Страница 20: ...2 Vane Motor Assembly 13 Filter 14 Fascia 15 Remote Handset 16 Control Box Lid 17 Control Box PCB 18 Control Box 19 Coil Bracket 20 Expansion Valve Enviromaster International LLC 5780 Success Drive Ro...

Отзывы: