background image

www.enviromaster.com

High Efficiency Condensing Units

9

18-36

09-15

SCC/SHC DIMENSIONS & SPECIFICATIONS

REFRIGERANT CHARGE TABLE FOR SCC/SHC

CONDENSER 

CAPACITY

EVAPORATOR 

PAIRING

LINE 

CHG/FT

LINE 

LENGTH

LINE 

ADJUST

FACTORY CHARGE

SYSTEM TOTAL

SCC

SHC

SCC

SHC

09

CHP 12

FHP 12

WHP 12

TBH 12

CAH 12

CNR 12

.25 OZ.

10

25

50

3 OZ.

6 OZ.

13 OZ.

26.5 OZ.

44 OZ.

29 OZ.

32 OZ.

39 OZ.

47 OZ.

50 OZ.

57 OZ.

12

CHP 12

FHP 12

WHP 12

TBH 12

CAH 12

CNR 12

.25 OZ.

10

25

50

3 OZ.

6 OZ.

13 OZ.

29.5 OZ.

42 OZ.

32 OZ.

35 OZ.

42 OZ.

45 OZ.

48 OZ.

55 OZ.

15

CHP 15

FHP 15

WHP 18 

CAH 24

.25 OZ.

10

25

50

3 OZ.

6 OZ.

13 OZ.

43.5 OZ.

52 OZ.

46.5 OZ.

49.5 OZ.

56.5 OZ.

55 OZ.

58 OZ.

65 OZ.

18

CHP 24

FHP 24

WHP 18

TBH 24

CAH 24

.56 OZ.

10

25

50

6 OZ.

14 OZ.

28 OZ.

35 OZ.

41 OZ.

41 OZ.

49 OZ.

63 OZ.

47 OZ.

55 OZ.

69 OZ.

24

CHP 24

FHP 24

WHP 30

TBH 24

CAH 24

.56 OZ.

10

25

50

6 OZ.

14 OZ.

28 OZ.

50 OZ.

44 OZ.

56 OZ.

64 OZ.

78 OZ.

50 OZ.

58 OZ.

72 OZ.

30

CHP 30

FHP 30

WHP 30

CAH 36

.56 OZ.

10

25

50

6 OZ.

14 OZ.

28 OZ.

64 oz.

68 oz.

70 OZ.

78 OZ.

92 OZ.

74 OZ.

82 OZ.

96 OZ.

36

CHP 36

FHP 36

WHP 36

CAH 36

.56 OZ.

10

25

50

6 OZ.

14 OZ.

28 OZ.

65 oz.

65 oz.

71 OZ.

79 OZ.

93 OZ.

71 OZ.

79 OZ.

93 OZ.

IMPORTANT NOTES:

1. To find the charge adjustment and system charge for any evaporator and tubing length:

Line Adjustment = (Line Charge/FT) x Line Length

System Total = Factory Line Adjustment

2. Round to the nearest ounce and allow for gauges and hoses.

MOUNTING DIMENSIONS

Содержание MC2 Series s

Страница 1: ...com INSTALLATION OPERATION AND MAINTENANCE MANUAL EMI AMERICASERIES SINGLE ZONE MULTI ZONE CONDENSING UNITS MC4 MH4 MULTI ZONE MC2 MH2 DUAL ZONE SCC SHC SINGLE ZONE STRAIGHT COOL HEAT PUMPS Nominal Ca...

Страница 2: ...er_________________________ Date of installation______________________ SAFETY INSTRUCTIONS Read all instructions before using the EMIAmericaSeries high ef ciency condensing unit Install or locate this...

Страница 3: ...may cause damage to the compressor and coil and could result in freezing that may void the warranty We accomplish the low ambient operation on our condensers by cycling the condenser fan When in low...

Страница 4: ...alent feet Whether the outdoor unit is above or below the indoor unit a P trap is recommended if the suction riser is 20 feet or higher NOTE Avoid excessive oil buildup The P trap should have a shallo...

Страница 5: ...panels and make sure they are properly secured Make nal visual inspection and repair any de ciencies NOTE A hard start kit may be required for units in low volt age frequent cycle applications OPERATI...

Страница 6: ...ommended for field charging or checking the existing refrigerant charge in a system Because each installation is different in terms of indoor air ow refrigerant line length etc the factory charge may...

Страница 7: ...80 198 5 215 5 235 0 203 5 212 0 226 0 237 0 85 208 5 230 5 252 0 218 0 227 0 242 5 253 0 90 223 0 246 0 270 0 233 5 241 5 259 0 270 0 95 241 5 263 0 285 0 250 5 256 0 275 5 285 0 100 264 0 280 5 300...

Страница 8: ...1 0 125 5 4 32 6 4 240 7 8 15 18EF 1 0 125 6 5 44 7 5 240 9 1 15 24EF 1 0 125 8 2 58 9 2 240 11 3 15 30EF 1 0 125 10 4 72 11 4 240 14 0 20 36EF 1 8 0 333 13 90 14 8 240 18 1 30 220 240 50 Hz 09FA 220...

Страница 9: ...52 OZ 46 5 OZ 49 5 OZ 56 5 OZ 55 OZ 58 OZ 65 OZ 18 CHP 24 FHP 24 WHP 18 TBH 24 CAH 24 56 OZ 10 25 50 6 OZ 14 OZ 28 OZ 35 OZ 41 OZ 41 OZ 49 OZ 63 OZ 47 OZ 55 OZ 69 OZ 24 CHP 24 FHP 24 WHP 30 TBH 24 CA...

Страница 10: ...rankcase heater This will offer protection against cold start situations thus prolonging the life of the compressor NOTE The crankcase heater is installed when the low ambient control option is select...

Страница 11: ...8 20 6 7 48 9 6 60 21 9 24 3 30 197 9508 1 8 0 33 3 8 20 6 7 48 7 4 48 19 7 21 6 25 197 2208 1 0 125 4 8 26 3 4 8 26 3 7 4 48 18 19 9 25 197 2008 1 0 125 4 8 26 3 7 4 48 13 2 15 1 20 197 9999 1 0 125...

Страница 12: ...erant charge protection NOTE The crankcase heater is installed with 9 15K Btu heat pumps and when the low ambient control option is selected MC2 MH2 DUAL ZONE High Ef ciency Condensing Unit Limited Ra...

Страница 13: ...0 0 125 4 8 26 3 4 8 26 3 10 6 11 8 15 9200 208 230 60 1 1 0 0 125 3 8 20 4 8 26 3 9 6 10 8 15 5500 208 230 60 1 1 8 0 25 6 4 38 6 4 38 14 6 16 2 20 1 Circuit Designators 9 9 000 Btuh 2 12 000 Btuh 5...

Страница 14: ...unit SCC SHC pg 8 MC4 MH4 pg 9 MC2 MH2 pg 11 or call the factory Anti short cycle protection should be used on systems that use a con ventional thermostat Evaporator Entering Air WB Evaporator Leaving...

Страница 15: ...others Failure to start due to voltage conditions blown fuses open circuit breakers or other damages due to the inadequacy or interruption of electrical service Damage or repairs needed as a consequen...

Страница 16: ...E mail emi enviromaster com Made in Rome New York USA 16...

Отзывы: