EMI  AMERICASERIES CONDENSING UNIT - COMMON SECTION

GENERAL RECOMMENDATIONS

Do not charge the 

straight cool

 units on cold days unless weigh-

ing in the charge. The 

heat pump

 systems may be charged in 

heat cycle at any temperature. 

These units uses a heat cycle 

TXV  and  cannot  be  charged  to  superheat;  use  weight  or 

subcooling method only.

Charging should be done with a dial-a-charge or weighed in with 

a scale.

SPECIFIC CHANGES

All EMI products are subject to ongoing development programs 

so design and specifications may change without notice. Please 
consult the factory for more information.

STARTING THE UNIT

• Before starting the unit in cool weather, power the system 

24 hours before attempting to start if a crankcase heater is 

installed.

•  Do  a  final  system  check  using  the  superheat/subcooling 

method. Record results on Test Unit Data Sheet.

• Remove gauge set. Mount all access panels and make sure 

they are properly secured. 

• Make final visual inspection and repair any deficiencies.

NOTE:

  

A hard start kit may be required for units in low volt-

age/frequent cycle applications.

OPERATION AND MAINTENANCE

The EMI AmericaSeries outdoor section is the compressor bearing 

unit of the system. It operates at the command of the  indoor sec-

tion or room thermostat. Therefore, the operation will be described 

in the manual pertaining to the indoor section.

EMI units are designed and constructed for reliability and long 

life with minimal maintenance. You can assure peak operating 

efficiency by regularly inspecting for free air passage into and 

through the coil. If debris collect on the air coil, it should be cleaned 

by "back-flushing" with a spray of water or vacuuming. 

TURN 

OFF POWER SUPPLY FIRST.

 Outdoor units may be cleaned or 

waxed if desired.  Use a non-abrasive car wax.

This unit is equipped with a permanently lubricated motor. Al-

though oiling is not necessary, adding a few drops through the 

oiling ports twice yearly will extend the life of the motor. Do not 

over oil.
Panels should remain on the unit at all times. Service should be 

performed by a QUALIFIED service agency only.

See Field Charging on following page.

Содержание MC2 Series s

Страница 1: ...com INSTALLATION OPERATION AND MAINTENANCE MANUAL EMI AMERICASERIES SINGLE ZONE MULTI ZONE CONDENSING UNITS MC4 MH4 MULTI ZONE MC2 MH2 DUAL ZONE SCC SHC SINGLE ZONE STRAIGHT COOL HEAT PUMPS Nominal Ca...

Страница 2: ...er_________________________ Date of installation______________________ SAFETY INSTRUCTIONS Read all instructions before using the EMIAmericaSeries high ef ciency condensing unit Install or locate this...

Страница 3: ...may cause damage to the compressor and coil and could result in freezing that may void the warranty We accomplish the low ambient operation on our condensers by cycling the condenser fan When in low...

Страница 4: ...alent feet Whether the outdoor unit is above or below the indoor unit a P trap is recommended if the suction riser is 20 feet or higher NOTE Avoid excessive oil buildup The P trap should have a shallo...

Страница 5: ...panels and make sure they are properly secured Make nal visual inspection and repair any de ciencies NOTE A hard start kit may be required for units in low volt age frequent cycle applications OPERATI...

Страница 6: ...ommended for field charging or checking the existing refrigerant charge in a system Because each installation is different in terms of indoor air ow refrigerant line length etc the factory charge may...

Страница 7: ...80 198 5 215 5 235 0 203 5 212 0 226 0 237 0 85 208 5 230 5 252 0 218 0 227 0 242 5 253 0 90 223 0 246 0 270 0 233 5 241 5 259 0 270 0 95 241 5 263 0 285 0 250 5 256 0 275 5 285 0 100 264 0 280 5 300...

Страница 8: ...1 0 125 5 4 32 6 4 240 7 8 15 18EF 1 0 125 6 5 44 7 5 240 9 1 15 24EF 1 0 125 8 2 58 9 2 240 11 3 15 30EF 1 0 125 10 4 72 11 4 240 14 0 20 36EF 1 8 0 333 13 90 14 8 240 18 1 30 220 240 50 Hz 09FA 220...

Страница 9: ...52 OZ 46 5 OZ 49 5 OZ 56 5 OZ 55 OZ 58 OZ 65 OZ 18 CHP 24 FHP 24 WHP 18 TBH 24 CAH 24 56 OZ 10 25 50 6 OZ 14 OZ 28 OZ 35 OZ 41 OZ 41 OZ 49 OZ 63 OZ 47 OZ 55 OZ 69 OZ 24 CHP 24 FHP 24 WHP 30 TBH 24 CA...

Страница 10: ...rankcase heater This will offer protection against cold start situations thus prolonging the life of the compressor NOTE The crankcase heater is installed when the low ambient control option is select...

Страница 11: ...8 20 6 7 48 9 6 60 21 9 24 3 30 197 9508 1 8 0 33 3 8 20 6 7 48 7 4 48 19 7 21 6 25 197 2208 1 0 125 4 8 26 3 4 8 26 3 7 4 48 18 19 9 25 197 2008 1 0 125 4 8 26 3 7 4 48 13 2 15 1 20 197 9999 1 0 125...

Страница 12: ...erant charge protection NOTE The crankcase heater is installed with 9 15K Btu heat pumps and when the low ambient control option is selected MC2 MH2 DUAL ZONE High Ef ciency Condensing Unit Limited Ra...

Страница 13: ...0 0 125 4 8 26 3 4 8 26 3 10 6 11 8 15 9200 208 230 60 1 1 0 0 125 3 8 20 4 8 26 3 9 6 10 8 15 5500 208 230 60 1 1 8 0 25 6 4 38 6 4 38 14 6 16 2 20 1 Circuit Designators 9 9 000 Btuh 2 12 000 Btuh 5...

Страница 14: ...unit SCC SHC pg 8 MC4 MH4 pg 9 MC2 MH2 pg 11 or call the factory Anti short cycle protection should be used on systems that use a con ventional thermostat Evaporator Entering Air WB Evaporator Leaving...

Страница 15: ...others Failure to start due to voltage conditions blown fuses open circuit breakers or other damages due to the inadequacy or interruption of electrical service Damage or repairs needed as a consequen...

Страница 16: ...E mail emi enviromaster com Made in Rome New York USA 16...

Отзывы: