Avoiding malfunction during loss of zero volts
To avoid accidental voltage errors at a safe output, the output circuit must always be
returned to the inverter 0 V terminal, and not to a 0 V connection elsewhere in the
system. If the safe output is not directly connected to the drive SAFE TORQUE OFF
then the following basic circuit should be used.
Figure 1-1 Loss of zero volts protection
1.18
Operation and service
Before installing and removing a module, or disconnecting signal lines, first isolate the
module electrically, i.e. shut it down.
While installing and removing a module, take appropriate precautions to prevent
electrostatic discharge on the externally routed terminals and plug connections.
1.19
Transportation / storage
Instructions regarding transportation, storage and proper handling must be followed.
Climate specifications must be observed in accordance with Table 8-1 on page 57.