71
July 2016
Reference Manual
00809-0200-4648, Rev BB
Special Condition for Safe Use (X):
1. The surface resistivity of the antenna is greater than
1 G
. To avoid electrostatic charge build-up, it must
not be rubbed or cleaned with solvents or a dry cloth.
2. The power module may be replaced in a hazardous
area. The power module has a surface resistivity
greater than 1 G
and must be properly installed in
the wireless device enclosure. Care must be taken
during transportation to and from the point of
installation to prevent electrostatic charge build-up.
International
I7
IECEx Intrinsic Safety
Certificate: IECEx BAS 07.0007X
Standards: IEC 60079-0: 2011, IEC 60079-11: 2011
Markings: Ex ia IIC T4 Ga, T4 (–60 °C
T
a
+70 °C)
Ex ia IIC T5 Ga, T5 (–60 °C
T
a
+40 °C)
Special Conditions for Safe Use (X):
1. The surface resistivity of the antenna is greater than
1 G
. To avoid electrostatic charge build-up, it must
not be rubbed or cleaned with solvents or a dry cloth.
2. The Model 701PBKKF Power Module may be replaced
in a hazardous area. The Power Modules have a
surface resistivity greater than 1 G
and must be
properly installed I the wireless device enclosure. Care
must be taken during transportation to and from the
point of installation to prevent electrostatic charge
build-up.
3. The Rosemount 648 Wireless enclosure may be made
of aluminum alloy and given a protective
polyurethane paint finish; however, care should be
taken to protect it from impact or abrasion if located
in a Zone 0 area.
Brazil
I2
INMETRO Intrinsic Safety
Certificate: UL-BR 15.0140X
Standards: ABNT NBR IEC 60079-0:2008 + Errata
1:2011, ABNT NBR IEC60079-11:2009
Markings: Ex ia IIC T4 (–60 °C
T
a
+70 °C),
Ex ia IIC T5(–60 °C
T
a
+40 °C) IP66
Special Condition for Safe Use (X):
1. See certificate for special conditions.
China
I3
China Intrinsic Safety
Certificate: GYJ11.1706X
Standards: GB3836.1-2010,
GB3836.4-2010,
GB3836.20-2010
Markings: Ex ia IIC T4/T5 Ga
Special Condition for Safe Use (X):
1. See certificate for special conditions.
Japan
I4
TIIS Intrinsic Safety
Certificates: TC18638
Markings: Ex ia IIC T4 (–20
~
+60 °C)
Special Condition for Safe Use (X):
1. See certificate for special conditions.
Sensor terminal parameters
U
O
= 6.6 V
I
O
= 26.2 mA
P
O
= 42.6 mW
C
o
= 11 μF
L
o
= 25 mH
Sensor terminal parameters
U
O
= 6.6 V
I
O
= 26.2 mA
P
O
= 42.6 mW
C
o
= 11 μF
L
o
= 25 mH
T code
Ambient temperature
T4
–60 °C
T
a
+70 °C
T5
–60 °C
T
a
+45 °C
Sensor terminal parameters
U
O
= 6.6 V
I
O
= 26.2 mA
P
O
= 42.6 mW
C
O
= 11 μF
L
O
= 25 μF
Sensor terminal parameters
U
O
= 6.6 V
I
O
= 26.2 mA
P
O
= 42.6 mW
C
O
= 11 μF
L
O
= 25 μF
Содержание Rosemount X-well 648
Страница 2: ......
Страница 6: ...vi Reference Manual 00809 0200 4648 Rev BB Title Page July 2016 Title Page ...
Страница 10: ...4 Reference Manual 00809 0200 4648 Rev BB Contents July 2016 Contents ...
Страница 12: ...2 Reference Manual 00809 0200 4648 Rev BB Introduction July 2016 Introduction ...
Страница 36: ...26 Reference Manual 00809 0200 4648 Rev BB Configuration July 2016 Configuration ...
Страница 52: ...42 Reference Manual 00809 0200 4648 Rev BB Commissioning July 2016 Commissioning ...
Страница 62: ...52 Reference Manual 00809 0200 4648 Rev BB Operation and Maintenance July 2016 Operation and Maintenance ...
Страница 66: ...56 Reference Manual 00809 0200 4648 Rev BB Troubleshooting July 2016 Troubleshooting ...
Страница 89: ......