Troubleshooting
July 2016
Troubleshooting
Electronics
Temperatures
has Exceeded
Limits
The electronics temperature has
exceeded the transmitter's
maximum range.
1. Verify environmental temperature is within the transmitter’s
range.
2. Remote mount the transmitter away from process and
environmental conditions.
3. Reset the device.
4. If the condition persists, replace the electronics.
Terminal
Temperature
has Exceeded
Limits
The terminal temperature has
exceed the transmitter's
maximum range.
1. Verify environmental temperature is within the transmitter’s
range.
3. Remote mount the transmitter away from process and
environmental conditions.
4. Reset the device.
5. If the condition persists, replace the electronics.
Supply Voltage
Low
The supply voltage is low and may
soon affect broadcast updates.
1. Replace the power module.
Database
Memory
Warning
The device has failed to write to
the database memory. Any data
written during this time may have
been lost.
1. Reset the device.
2. Reconfirm all configuration items in the device.
3. If logging dynamic data not needed, this advisory can be
safely ignored.
4. If the condition persists, replace the electronics.
Invalid
Configuration
The device has detected a
configuration error based on a
change to the device.
1. Select details for more information.
2. Correct the parameter that has a configuration error.
3. Reset the device.
4. If the condition persists, replace the electronics.
HI HI Alarm
The primary variable has
surpassed the user defined limit.
1. Verify the process variable is within user specified limits.
2. Reconfirm the user defined alarm limit.
3. If not needed, disable this alert.
HI Alarm
The primary variable has
surpassed the user defined limit.
1. Verify the process variable is within user specified limits.
2. Reconfirm the user defined alarm limit.
3. If not needed, disable this alert.
Lo Alarm
The primary variable has
surpassed the user defined limit.
1. Verify the process variable is within user specified limits.
2. Reconfirm the user defined alarm limit.
3. If not needed, disable this alert.
Lo Lo Alarm
The primary variable has
surpassed the user defined limit
1. Verify the process variable is within user specified limits.
2. Reconfirm the user defined alarm limit.
3. If not needed, disable this alert.
Button Stuck
A button on the Electronic Board is
detected as stuck in the active
position.
1. Check the buttons for obstructions.
2. Reset the device.
3. If conditions persist, replace the electronics.
Simulation
Active
The device is in simulation mode
and may not be reporting actual
information.
1. Verify simulation is no longer required.
2. Disable Simulation mode in Service Tools.
3. Reset the device.
Table 6-1. Rosemount
™
648 Wireless Temperature Transmitter Device Status Information
Device status
Description
Recommended action
Содержание Rosemount X-well 648
Страница 2: ......
Страница 6: ...vi Reference Manual 00809 0200 4648 Rev BB Title Page July 2016 Title Page ...
Страница 10: ...4 Reference Manual 00809 0200 4648 Rev BB Contents July 2016 Contents ...
Страница 12: ...2 Reference Manual 00809 0200 4648 Rev BB Introduction July 2016 Introduction ...
Страница 36: ...26 Reference Manual 00809 0200 4648 Rev BB Configuration July 2016 Configuration ...
Страница 52: ...42 Reference Manual 00809 0200 4648 Rev BB Commissioning July 2016 Commissioning ...
Страница 62: ...52 Reference Manual 00809 0200 4648 Rev BB Operation and Maintenance July 2016 Operation and Maintenance ...
Страница 66: ...56 Reference Manual 00809 0200 4648 Rev BB Troubleshooting July 2016 Troubleshooting ...
Страница 89: ......