24
Reference Manual
00809-0200-4648, Rev BB
July 2016
View Rosemount X-well measurement details
To view live data and trending for measured ambient temperature, measured surface
temperature, and calculated process temperature, perform the following procedure:
1.
Right click on the device and select
Configure
.
2.
In the menu tree, select
Manual Setup
.
3.
Select the
Sensor
tab.
4.
Select the
Measurement Details
button.
Figure 2-15. Rosemount X-well Measurement Details Page
2.9.3
Process alerts
Process alerts allow the user to configure the transmitter to output a HART message when
the configured data point is exceeded. An alert will be transmitter continuously if the set
points are exceeded and the alert mode is ON. An alert will be displayed on a Field
Communicator, AMS Device Manager status screen or in the error section of the LCD
display. The alert will reset once the value returns within range.
Note
HI alert value must be higher than the LO alert value. Both alert values must be within the
temperature sensor limits.
Fast Key sequence
2, 1, 7
Содержание Rosemount X-well 648
Страница 2: ......
Страница 6: ...vi Reference Manual 00809 0200 4648 Rev BB Title Page July 2016 Title Page ...
Страница 10: ...4 Reference Manual 00809 0200 4648 Rev BB Contents July 2016 Contents ...
Страница 12: ...2 Reference Manual 00809 0200 4648 Rev BB Introduction July 2016 Introduction ...
Страница 36: ...26 Reference Manual 00809 0200 4648 Rev BB Configuration July 2016 Configuration ...
Страница 52: ...42 Reference Manual 00809 0200 4648 Rev BB Commissioning July 2016 Commissioning ...
Страница 62: ...52 Reference Manual 00809 0200 4648 Rev BB Operation and Maintenance July 2016 Operation and Maintenance ...
Страница 66: ...56 Reference Manual 00809 0200 4648 Rev BB Troubleshooting July 2016 Troubleshooting ...
Страница 89: ......