5. Using the box provided on the nameplate, the User shall permanently mark the
type of protection chosen for the specific installation. Once the type of protection
has been marked it shall not be changed.
6. The applicable temperature class, ambient temperature range and process
temperature range of the equipment is as follows:
Temperature class /
Maximum surface
temperature
Ambient temperature range
Process temperature range
Gas groups:
T2
-60 °C ≤ Ta ≤ 70 °C
-60 °C to 250 °C
T3
-60 °C ≤ Ta ≤ 70 °C
-60 °C to 195 °C
T4
-60 °C ≤ Ta ≤ 70 °C
-60 °C to 130 °C
Dust groups:
T250°C
-60 °C ≤ Ta ≤ 70 °C
-60 °C to 250 °C
T200°C
-60 °C ≤ Ta ≤ 70 °C
-60 °C to 195 °C
T135°C
-60 °C ≤ Ta ≤ 70 °C
-60 °C to 130 °C
T100°C
-60 °C ≤ Ta ≤ 70 °C
-60 °C to 95 °C
T85°C
-60 °C ≤ Ta ≤ 70 °C
-60 °C to 80 °C
B.12.3
N7 IECEx Type N: Non-Sparking
Certificate
IECEx FMG15.0033X
Standards
IEC 60079-0:2017, IEC 60079-15:2010, IEC 60529:2013
Markings
Ex nA IIC T4…T2 Gc
(-34 °C ≤ Ta ≤ +70 °C), IP65
V ≤ 42.4V, I ≤ 23 mA
Specific Conditions of Use (X):
1. The Model 5408 Level Transmitter will not pass the 500Vrms dielectric strength test
between the circuits and the earth ground. This must be taken into account during
installation.
2. Plastic wire-on tag, Plastic part of Process Seal Antenna and Non-standard paint
options (paint options other than Rosemount Blue) may cause risk from
Electrostatic discharge. Avoid installation that could cause electrostatic build-up,
and only clean with a damp cloth.
3. Cable entries must be used which maintain the ingress protection of the enclosure
to at least IP65. To maintain the ingress protection ratings, Covers and Sensor
Module to be fully tightened and PTFE tape or pipe dope is required for cable entries
and blanking plugs. See Instruction Manual on application requirements.
4. The applicable temperature class, ambient temperature range and process
temperature range of the equipment is as follows:
Reference Manual
Product certifications
00809-0100-4408
February 2020
Rosemount 5408 and 5408:SIS Level Transmitters
227
Содержание Rosemount 5408
Страница 4: ...4 ...
Страница 8: ...Contents Reference Manual February 2020 00809 0100 4408 viii Reference Manual ...
Страница 10: ...Introduction Reference Manual February 2020 00809 0100 4408 10 Reference Manual ...
Страница 20: ...Transmitter overview Reference Manual February 2020 00809 0100 4408 20 Reference Manual ...
Страница 72: ...Mechanical installation Reference Manual February 2020 00809 0100 4408 72 Reference Manual ...
Страница 100: ...Operation Reference Manual February 2020 00809 0100 4408 100 Reference Manual ...
Страница 240: ...Product certifications Reference Manual February 2020 00809 0100 4408 240 Reference Manual ...
Страница 242: ...Product certifications Reference Manual February 2020 00809 0100 4408 242 Reference Manual ...
Страница 244: ...Product certifications Reference Manual February 2020 00809 0100 4408 244 Reference Manual ...
Страница 246: ...Product certifications Reference Manual February 2020 00809 0100 4408 246 Reference Manual ...
Страница 248: ...Product certifications Reference Manual February 2020 00809 0100 4408 248 Reference Manual ...