Procedure
1. Turn the jam screw clockwise until it is completely threaded into the housing.
H2.5 mm
2. Remove the cover.
3. Remove the blue plug from the TEST terminal.
4. Connect the ampere meter leads to the terminals labeled “+” and “TEST”.
5. Measure the loop current.
Reference Manual
Service and troubleshooting
00809-0100-4408
February 2020
Rosemount 5408 and 5408:SIS Level Transmitters
125