RSTI-EP PROFINET I/O Controller User Manual
Section 5
GFK-2571R
May 2021
Diagnostics
118
Group/
Category/
Type/
Descriptor
Description
Cause
Recommended
Correction
7-36-1-0
Network port
released by
PROFINET IO
Supervisor.
A configured
PROFINET port
that was
previously
controlled by a
PROFINET IO
Supervisor has
been released.
None.
9-6-10-0
Multiple
Media
Redundancy
Managers
have been
detected on
the network.
The PROFINET
Controller is
configured as a
Media
Redundancy
Manager and
other Media
Redundancy
Managers are
currently
present on the
network.
Update the PROFINET Controller configuration
to change its MRP role to either Disabled or
Client or remove all the other devices on the
network that are also acting as a Media
Redundancy Manager.
9-6-11-0
Multiple
Media
Redundancy
Managers are
no longer
present on the
network.
The PROFINET
Controller
is
configured as a
Media
Redundancy
Manager and it
had
detected
that
multiple
Media
Redundancy
Managers were
on the network,
but now those
other managers
are no longer
present.
No action necessary. The network is expected
to only have a single Media Redundancy
Manager present.
9-6-12-0
The Media
Redundancy
Manager has
detected that
the network
ring has been
broken.
The PROFINET
MRP
network
ring is broken.
The MRP Ethernet ring is broken. Possible
causes include damaged or disconnected cable
or power loss to a node or switch. Locate and
repair the cause(s).
Содержание PACSystems RX3i
Страница 1: ...USER MANUAL GFK 2571R May 2021 PACSystemsTM RX3i and RSTi EP PROFINET I O CONTROLLER USER MANUAL ...
Страница 46: ...RSTI EP PROFINET I O Controller User Manual Section 2 GFK 2571R May 2021 Installation 39 ...
Страница 51: ...RSTI EP PROFINET I O Controller User Manual Section 2 GFK 2571R May 2021 Installation 44 ...
Страница 72: ...RSTI EP PROFINET I O Controller User Manual Section 3 GFK 2571R May 2021 Configuration 65 ...
Страница 82: ...RSTI EP PROFINET I O Controller User Manual Section 3 GFK 2571R May 2021 Configuration 75 ...