42
5
OK LED solid
green
Normal operation. Power up
completed and backplane
communications established.
OK LED blinks
green (1 Hz)
Module power-up completed,
but communication not yet
established over the RX3i
backplane.
Note:
Under certain ambient operating temperatures, the PROFINET Controller may momentarily
display the overtemperature pattern during power up, while it is calibrating its thermal
protection functions. This indication may be ignored, and no overtemperature entry is added
to the Local Log table, the Controller Fault Table or I/O Fault Table.
For details, see Special LED Pattern - Module Identification in Section 5:, Diagnostics.
2.8.2
Detailed LED Descriptions
OK LED
The OK LED indicates whether the module can perform normal operation.
Green, ON
OK
Green, blink pattern
Fatal error. Flashes once between error codes
blinked on the
OK
LED
Amber, blink pattern
Fatal error
OFF
Not OK
LAN LED
The LAN LED indicates access to and activity on the Ethernet network. The LAN LED indicates
network packets are being processed by the network interface (not just passing through the
embedded switch).
Blinking ON
The module’s network interface is active
Blink pattern
Fatal error. Flashes once between error codes
blinked on the
OK
LED
OFF
No activity
STATUS LED
The STATUS LED indicates the condition of the PROFINET Controller during normal
operation. It indicates whether an entry other than the startup event is present in the
module’s Local Log. STATUS can also indicate whether any of the MAC addresses are invalid.
The STATUS LED state is reset when the Local Log is cleared. For more information see the
Command Line Interface clear log command.
Green, ON
No new Local Log table entries
Содержание PACSystems RX3i
Страница 1: ...USER MANUAL GFK 2571R May 2021 PACSystemsTM RX3i and RSTi EP PROFINET I O CONTROLLER USER MANUAL ...
Страница 46: ...RSTI EP PROFINET I O Controller User Manual Section 2 GFK 2571R May 2021 Installation 39 ...
Страница 51: ...RSTI EP PROFINET I O Controller User Manual Section 2 GFK 2571R May 2021 Installation 44 ...
Страница 72: ...RSTI EP PROFINET I O Controller User Manual Section 3 GFK 2571R May 2021 Configuration 65 ...
Страница 82: ...RSTI EP PROFINET I O Controller User Manual Section 3 GFK 2571R May 2021 Configuration 75 ...