RSTI-EP PROFINET I/O Controller User Manual
Section 5
GFK-2571R
May 2021
Diagnostics
121
Group/
Category/
Type/
Descriptor
Description
Cause
Recommended
Correction
9-71-0-0
Duplicate IP
Address
detected on
the network.
PROFINET
Controller has
detected a
duplicate IP
Address on the
network. The
location
associated with
the fault will
indicate
whether the
duplication is
with the
PROFINET
Controller itself,
or with a
configured
PROFINET
Device.
Either remove the device on the network that
has the duplicate IP Address, or assign a new IP
Address to either the PROFINET Controller or
the conflicting device.
Note:
The Fault Extra Data displays the MAC
addresses of the conflicting devices in
the MAC 1 field (bytes 8
–
13) and the
MAC 2 field (bytes 14
–
19). If the
PROFINET Controller is one of the
devices with a conflicting IP Address,
MAC 1 will be 0. This data is stored in Big
Endian (most significant byte in lowest
address)
format.
Also, if the conflict is between PROFINET
devices on the network, the DCP Tool
can be used to help find the conflict.
Sorting by IP Address within the tool
may make it easier to identify the
duplicates.
9-72-0-0
Duplicate IP
Address
conflict
resolved.
PROFINET
Controller has
detected that a
previously
duplicated IP
Address conflict
has been
resolved. The
location
associated with
the fault will
indicate
whether the
duplication was
with the
PROFINET
Controller itself,
or with a
configured
PROFINET
Device.
None.
Содержание PACSystems RX3i
Страница 1: ...USER MANUAL GFK 2571R May 2021 PACSystemsTM RX3i and RSTi EP PROFINET I O CONTROLLER USER MANUAL ...
Страница 46: ...RSTI EP PROFINET I O Controller User Manual Section 2 GFK 2571R May 2021 Installation 39 ...
Страница 51: ...RSTI EP PROFINET I O Controller User Manual Section 2 GFK 2571R May 2021 Installation 44 ...
Страница 72: ...RSTI EP PROFINET I O Controller User Manual Section 3 GFK 2571R May 2021 Configuration 65 ...
Страница 82: ...RSTI EP PROFINET I O Controller User Manual Section 3 GFK 2571R May 2021 Configuration 75 ...