RSTI-EP PROFINET I/O Controller User Manual
Section 1
GFK-2571R
May 2021
Introduction
11
Topic
-Ax
-Bxxx
Appearance
Figure 3
Case
Plastic
Metal
Attachment to Rack
Via plastic case latch and
heatsink screw
Via two Phillip’s head machine
screws
Heatsink
Remove plastic knockout from
rack
No knockout removal required
Status LEDs
6 LEDs
5 LEDs (no USB LED)
LED Behavior
See Section 2.8
See Section 2.8
Ethernet Port LEDs
4 singleton LEDs (top of
faceplate)
4 banks of LEDs (bottom of
faceplate)
The digits representing the port
numbers are backlit by LEDs.
µUSB Port
Present
Absent
Command Line Interface Uses Micro USB Port
Not available
RJ45 Connector on
Faceplate
Absent
Present (Disabled)
Power Requirements
Higher (see Section 1.3)
Lower (see Section 1.3)
Operating Temperature
Range (Surrounding Air)
0 to 60°C
-25 to 60°C
Module Reset
Pushbutton “Restart”
Membrane “Reset”
With the Exception for the Command Line Interface, the -Bxxx version is functionally
compatible with the -Ax version.
1.5.2
Ethernet Network Ports
Figure 4 shows the underside of the PNC001 module.
•
Ports 1 and 2 are standard RJ45 connections.
•
Ports 3 and 4 offer Small Form-factor Pluggable (SFP) cages
The PROFINET Controller connects to a PROFINET network via one or more of its four
external switch ports. Two 8-conductor RJ45 shielded twisted pair 10/100/1000 Mbps
copper interfaces and two SFP cages provide flexibility in media selection and the ability to
use redundant media for the PROFINET network. Use of redundant media must first be set
up in the module configuration. Section 6: provides additional information about
Redundant Media.
The PROFINET protocol supported by the PACSystems RX3i PROFINET modules can be sent
and received over any of the four external ports on PNC001.
The PNC001 module is assigned five Ethernet MAC addresses: one for each of the four
external Ethernet ports and one for the internal switch.
Содержание PACSystems RX3i
Страница 1: ...USER MANUAL GFK 2571R May 2021 PACSystemsTM RX3i and RSTi EP PROFINET I O CONTROLLER USER MANUAL ...
Страница 46: ...RSTI EP PROFINET I O Controller User Manual Section 2 GFK 2571R May 2021 Installation 39 ...
Страница 51: ...RSTI EP PROFINET I O Controller User Manual Section 2 GFK 2571R May 2021 Installation 44 ...
Страница 72: ...RSTI EP PROFINET I O Controller User Manual Section 3 GFK 2571R May 2021 Configuration 65 ...
Страница 82: ...RSTI EP PROFINET I O Controller User Manual Section 3 GFK 2571R May 2021 Configuration 75 ...