RSTI-EP PROFINET I/O Controller User Manual
Section 1
GFK-2571R
May 2021
Introduction
6
Specification
Description
Number of PROFINET Port
Connectors
PNC001
–
2 RJ45 and 2 SFP Cages located on the underside of
module
(SFP devices not included, available separately).
Embedded PROFINET IO-Controller
–
2 RJ45.
Front Panel Connectors
PNC001-Ax: One micro USB for communication with a computer
using Command Line Interface.
PNC001-Bxxx: One RJ45. Disabled.
Command Line Interface
Supported
PNC001-Ax
–
Yes. PNC001-Bxxx: No.
Embedded PROFINET IO-Controller
–
No.
LAN
IEEE 802.2 Logical Link Control Class I
IEEE 802.3 CSMA/CD Medium Access Control 10/100/1000 Mbps
Maximum I/O Memory
128 Kbytes of combined input/output memory per PROFINET
Controller
Note:
RSTi-EP CPE100/CPE115 supports a maximum of 8 IO
Devices. The combined input and output memory are
equivalent to the input /output memory requirements
of those 8 devices.
Hot-swappable
PNC001
–
Yes;
Embedded PROFINET IO-Controller
–
No.
CPU Status Bits
32
PROFINET IO-Device Data
Update Rates on the
PROFINET Network
Configurable: 1ms, 2ms, 4ms, 8ms, 16ms, 32ms, 64ms, 128ms,
256ms and 512ms
Note:
For CPE100/CPE115, Update Rates below 16ms are
not recommended.
Number of IP Addresses
One
Number of MAC Addresses
PNC001
–
5. One per external PROFINET port and one internal.
Embedded PROFINET IO-Controller
–
1.
System Maximum Limits
PROFINET Controllers per
RX3i CPU
Four PNC001 maximum. Must be in main CPU rack. Cannot be in a
remote node.
CPE330 supports one embedded PROFINET Controller plus up to
four PNC001.
CPL410, CPE400 & CPE100/CPE115 support one embedded
PROFINET Controller. Since these are standalone CPUs, they do not
support any PNC001 in their hardware configuration.
Max IO-Devices per
IO-Controller (at the
maximum update rate
interval, 16ms to 256ms)
PNC001
–
128
CPE330/CPE400
–
32 (simplex) or 20 (Hot Standby Redundancy)
CPL410
–
64 (simplex) or 32 (Hot Standby Redundancy)
RSTi-EP CPE100/CPE115
–
8
For limits at shorter update intervals, refer to PROFINET Controller
Loading Limits in Section 3.
Содержание PACSystems RX3i
Страница 1: ...USER MANUAL GFK 2571R May 2021 PACSystemsTM RX3i and RSTi EP PROFINET I O CONTROLLER USER MANUAL ...
Страница 46: ...RSTI EP PROFINET I O Controller User Manual Section 2 GFK 2571R May 2021 Installation 39 ...
Страница 51: ...RSTI EP PROFINET I O Controller User Manual Section 2 GFK 2571R May 2021 Installation 44 ...
Страница 72: ...RSTI EP PROFINET I O Controller User Manual Section 3 GFK 2571R May 2021 Configuration 65 ...
Страница 82: ...RSTI EP PROFINET I O Controller User Manual Section 3 GFK 2571R May 2021 Configuration 75 ...