![background image](http://html.mh-extra.com/html/emerson/pacsystems-rx3i/pacsystems-rx3i_user-manual_101411038.webp)
RSTI-EP PROFINET I/O Controller User Manual
Section 2
GFK-2571R
May 2021
Installation
31
2.4
Module Installation
•
RX3i rack power may be off or on (see Hot Insertion and Removal for details).
•
Holding the module firmly, align the module with the correct slot and connector.
•
Engage the module’s rear pivot hook in the notch on the top of the backplane
(1).
•
Swing the module down (2) until the module’s connector engages the backplane’
s
backplane connector, and the release lever (PNC001-Ax only) on the bottom of the
module snaps into place in the bottom module retainer (3).
•
Visually inspect the module to be sure it is properly seated.
•
PNC001-Ax: Tighten the heat sink screw on the front of the module in the threaded hole
in the back plate to 6 in-lbs (0.68 Nm), using a flat-tip screwdriver.
•
PNC001-Bxxx: Secure the bottom of the module to the backplane using the two captive
Phillip’s head machine screws provided with
the module (not shown in diagram).
Figure 19: Install Module into RX3i Backplane
Содержание PACSystems RX3i
Страница 1: ...USER MANUAL GFK 2571R May 2021 PACSystemsTM RX3i and RSTi EP PROFINET I O CONTROLLER USER MANUAL ...
Страница 46: ...RSTI EP PROFINET I O Controller User Manual Section 2 GFK 2571R May 2021 Installation 39 ...
Страница 51: ...RSTI EP PROFINET I O Controller User Manual Section 2 GFK 2571R May 2021 Installation 44 ...
Страница 72: ...RSTI EP PROFINET I O Controller User Manual Section 3 GFK 2571R May 2021 Configuration 65 ...
Страница 82: ...RSTI EP PROFINET I O Controller User Manual Section 3 GFK 2571R May 2021 Configuration 75 ...