Chapter 6 Use Of Monitoring Module M501D 85
displayed in the form of capacity percentage, remaining Ah number and the remaining time. The default display is the
capacity percentage, as shown in the above figure.
During the normal boost charge/float charge management, the monitoring module will take the nominal capacity of
the single battery pack as the full capacity of the battery pack. During the discharge of the battery, the monitoring
module will obtain the real time remaining capacity of the battery according to the detected discharge current and
discharge time. During the charge of the battery, the monitoring module will obtain the remaining capacity of the
battery by calculating the charged capacity according to the detected charge current and charge time. If the
calculated remaining capacity of the battery is higher than the nominal capacity, the monitoring module will
automatically calibrate the real time remaining capacity of the battery to be the nominal capacity.
AC information screen
The maximal and minimal voltage values of all the rectifier AC inputs for the power system will be displayed.
Rect AC Volt
Max Volt: 221
Min Volt: 220
BC prompt page
Used Capacity:
80.2%
Next Cyc Boost:
2397h
If the monitoring module disables boost charge or boost charge is being conducted, ‘0h’ will be displayed.
Temperature information screen
Bat. Temp:
None
Amb. Temp:
None
If the monitoring module has not been configured with the temperature sensor, the screen will not be displayed.
The temperature information detected by the temperature sensor will differ with different parameter configurations.
For details about the parameter configuration, please refer to
. If the temperature sensor has not
been connected or fails in measurement, ‘invalid’ will be prompted.
6.4 Querying Rectifier Status
The module information includes the serial number of the rectifier, the voltage, current, current limiting threshold of
each module, the AC/DC status of the switch, the module-limited power, and the temperature-limited power.
1. At any system information page, press ENT to enter the main menu.
2. Use ▲ or ▼ keys to select the ‘Status’ sub-menu in the main menu, and press ENT to confirm.
STATUS
Rectifiers
Active Alarm
Alarm History
3. Use ▲ or ▼ to select the ‘Rectifiers’ submenu, as shown in the above figure. Press ENT to confirm.
NetSure 501 A50, NetSure 501 AA0, NetSure 701 A51 19-Inch Subrack Power Supply System User Manual