Chapter 6 Use Of Monitoring Module M501D 97
Float: 53.5V
Boost : 56.4V
Limit : 0.100C10
Over : 0.300C10
Start Boost
Automatic: Y
Cyclic: Y
Automatic Boost
Curr: 0.060C10
Capacity:
80%
Constant Boost
Curr: 0.010C10
Duration:
180min
Cyclic Boost
Interval: 2400h
Duration:
7200min
Use ▼ or ▲ to select one page or one of the parameters, and ◄ or ► to select the parameter value. Press ENT to
confirm and save.
15. Note
Normally, the user shall retain the default value of the parameter instead of performing additional setting.
The value of charging management parameters is described in the following table.
Table 1.3 Description of charging management parameters
Parameter
Setting
range
Default
value
Value description
Float voltage
42V
to
58V
53.5V
In the float charging status, all rectifiers output voltage
according to the setting value of ‘Float charging voltage’
The setting value of ‘Boost
charging voltage’ must be
higher than that of ‘Float
charging voltage’
Boost voltage
56.4V
In the boost charging status, all rectifiers output voltage
according to the setting value of ‘Boost charging
voltage’
Current limit
0.1
to
0.25C
10
0.1C
10
The monitoring module detects the charging current of the battery. If the charging
current is higher than the setting value of the ‘current limit point’, the monitoring
module will send current limit control command to limit the charging current of the
battery.
C
10
indicates nominal capacity of battery, and is usually set to 10~20% of the capacity
of single pack of batteries
Over current
0.3C
10
to
1.0C
10
0.300C
1
0
The monitoring detects the charging current of the battery. If the charging current is
higher than the setting value of the ‘over current point’, the monitoring module will
generate alarm o battery charging over current
Automatic boost
charging
enabled
Yes, No
Yes
If selecting ‘Enabled’, the system meets the boost charging conditions and can be
boost charged
Timing boost
charging
enabled
If selecting ‘Enabled’, after the time in which the power system has been in the float
charging status reaches that set in the ‘Timing boost charging period’, the monitoring
module will control the power system to conduct timing boost charging. The battery
charging voltage is setting value of ‘charging voltage’ and the charging time is setting
value of ‘Timing boost charging duration’
Timing boost
charging period
48 to 8760
hours
2400
hours
Timing boost
charging
duration
30 to 2880
minutes
720
minutes
Boost charging
conversion
current
0.50
to
0.80C
10
0.06C
10
When the battery capacity reduces to the setting value of ‘Boost charging conversion
capacity’, or when the charging current reaches the setting value of ‘Boost charging
conversion current’, the monitoring module switches the system to the boost charging.
The battery charging voltage is the setting value of ‘Boost charging voltage’
Boost charging
conversion
capacity
0.1 to 0.95
0.80
CONSTANT
boost charging
current
0.02 to
0.99C10
0.01C
10
When the system is in the boost charging status, if the charging current is as low as
the setting value of ‘Constant boost charging current’, the system will automatically
transfer to the boost charging after the time set in the ‘Constant boost charging time’.
The battery charging voltage is the setting value of ‘Float charging voltage’
CONSTANT
boost charging
time
30 to 1440
minutes
180
minutes
NetSure 501 A50, NetSure 501 AA0, NetSure 701 A51 19-Inch Subrack Power Supply System User Manual