42 Chapter 5 Use Of Monitoring Module M800D
Rated Voltage
53.50 V
Rated Current
50.5 A
The settable parameters of the rectifier are displayed in one more screen. Press ▲ or ▼ to scroll through the
screens:
Rated Over Volt
59.50 V
Rated Low Volt
40.5 V
Method of configuring the parameters
With the “Rect Over Volt” configuring as an example, press ▲ or ▼ to move the cursor to the value of “Rect Over
Volt” (59.50V) and press ENT to highlight the row. Press ◄ or ► to change the value. The change step of the value is
configurable. After modifying the parameter, press ENT to validate the modification.
Method of configuring the status
WALKIn Enable
Enabled
Redundancy Enb
Enabled
With “WALKIn Enable” as an example, press ▲ or ▼ to move the cursor to the value of “WALKIn Enable” and press
ENT to highlight the row. Press ◄ or ► to change the value (from “Enable” to “Disable”, or from “Disable” to
“Enable”).
If the equipment category has more than one piece of equipment, the detailed settable parameters of the equipment
are displayed in two-level menus. Press ◄ or ► to view the information of other equipment that belongs to the
equipment category.
Alarm parameter setting
The alarm parameter setting screen is shown in the following figure.
Parameter Set
SMIO 8
Alarm Param
System Param
In the preceding screen, press ▲ or ▼ to move the cursor to the menu of “Alarm Param” and press ENT, the
following screen pops up:
Alarm Control
Alarm Param
Alarm Level
In the preceding screen, press ▲ or ▼ to move the cursor to the menu of “Alarm Level” and press ENT, the following
screen pops up to allow the user to set the alarm level:
Alarm Level
M800D System
Rect Group
Rectifier
Method of setting the alarm level:
NetSure 501 A50, NetSure 501 AA0, NetSure 701 A51 19-Inch Subrack Power Supply System User Manual