Installation and start-up procedures 63
25A Switch Mode Rectifier
NT5C06B / C Installation and User Manual
Note:
If the desired HVSD level is greater than the –57 V float
limit, hold the FLT/EQL switch to EQL and use the
EQL potentiometer to bring the float voltage to the
desired HVSD level. Hold the switch through the
following steps.
Float voltage adjustment
Note:
For installation where rectifiers can be connected to the
charge bus (all rectifiers with DC breakers ON and
remote sense leads connected) prior to final adjustment,
Procedure 13 can be omitted and be performed in the
“Parallel verification” procedure section.
Procedure 13 - Float voltage adjustment
Step Action
1
Adjust the float potentiometer FLT to 0.5 volt DC (see
Note
below) above
the desired float voltage determined by the battery vendor or power
engineer, using the voltmeter attached to the test point (V+ V-).
2
Final system’s float voltage adjustment will be performed as indicated in
“Parallel verification” Procedure15, step 4.
–
end–
Note:
The 0.5 volt DC extra does not apply to MPR25 rectifiers
of a release above Rel: 30.
Equalize voltage adjustment
Procedure 14 - Equalize voltage adjustment
Step Action
1
Hold the equalize switch in the EQL position.
2
While the switch is up, set the equalize potentiometer to 0.5 volts DC
(see
Note
below) above the desired level determined by the battery
vendor or power engineer, using the voltmeter attached to the test point
(V+ V-).
–end–
Note:
The 0.5 volt DC extra does not apply to MPR25 rectifiers
of release above Rel: 30.
Содержание MPR15 Series
Страница 2: ......
Страница 4: ......
Страница 80: ...80 Maintenance UM5C06B C 169 2071 500 P0711722 Standard 10 00 May 2001 This page is left blank intentionally ...
Страница 100: ...100 References UM5C06B C 169 2071 500 P0711722 Standard 10 00 May 2001 This page is left blank intentionally ...
Страница 118: ...118 Abbreviations and acronyms 167 2071 500 Standard 8 0 May 1999 This page is left blank intentionally ...
Страница 119: ......