Operation 39
25A Switch Mode Rectifier
NT5C06B / C Installation and User Manual
Output current:
one rectifier
25 A
two rectifiers
50 A
three rectifiers
75 A
Note that when three phase 208 / 240 V AC lines are used to power more
than one shelf, it is preferable to distribute the shelves equally among the
phases.
Use a 20 A breaker or FRN type fuse for individual AC.
Use a 40 A breaker or FRN type fuse for two rectifiers, common AC.
Use a 60 A breaker or FRN type fuse for three rectifiers, common AC.
When using the MPR15 rectifier powered from 120 V AC, the power shelf
equipped with one, two, or three rectifiers has the following specifications:
Condition:
Typical input current value for 54 V dc, full load
output.( ) = maximum input current at Output 54 V dc, current limit
minimum line
Input Voltage:
120 V AC
Frequency: 47-63
Hz
Range:
96-132 V AC
Input Current:
one rectifier
10.5 (16.5)
two rectifiers
21.0 (33.0)
three rectifiers
31.5 (49.5)
Use a 20 A breaker or FRN type fuse for individual AC.
Use a 40 A breaker or FRN type fuse for two rectifiers, common AC.
Use a 60 A breaker or FRN type fuse for three rectifiers, common AC.
Output Voltage:
-46 V DC to -57 V DC
Output current:
one rectifier
15 A
two rectifiers
30 A
three rectifiers
45 A
Содержание MPR15 Series
Страница 2: ......
Страница 4: ......
Страница 80: ...80 Maintenance UM5C06B C 169 2071 500 P0711722 Standard 10 00 May 2001 This page is left blank intentionally ...
Страница 100: ...100 References UM5C06B C 169 2071 500 P0711722 Standard 10 00 May 2001 This page is left blank intentionally ...
Страница 118: ...118 Abbreviations and acronyms 167 2071 500 Standard 8 0 May 1999 This page is left blank intentionally ...
Страница 119: ......