58 Installation and start-up procedures
UM5C06B / C ( 169-2071-500 ) P0711722 Standard 10.00 May 2001
CAUTION
Operating voltage
If the NT5C06CB, CD or CE model is used, ensure that
the nominal line voltage is 110 V AC. Operating the unit
at 208 / 240 V AC will damage the unit.
Cabling the rectifier
The AC and DC cabling to the rectifier is provided directly by an internal
wire harness in the power shelf.
Figure 21 - Rectifier AC and DC power (internal) cabling harness
DC +
DC -
GND
AC
AC
12 AWG
12 AWG
12 AWG
12 AWG
12 AWG
12 AWG
12 AWG
12 AWG
12 AWG
12 AWG
BLACK
]
RED
]
GREEN
]
BLACK
]
WHITE
]
CONNECTOR: AMP
530521-9
CONTACTS: AMP
530520-1
KEYING PLUG: AMP
530533-1
(NOTE)
Noten:
When required, keying plugs (CPC A0377927) can be
ordered. Insert one in the third plug from the bottom
.
The rectifier frame is grounded through the 12 AWG green wire of the wire harness.