172
Mentor MP User Guide
www.controltechniques.com Issue: 3
S.OV
Excessive suppressor voltage
172
Operation of the drive requires the installation of the external suppressor resistance, see section 4.7
t002
Reserved
2
A value of 2 is being written to user trip (Pr
10.38
). The drives internal logic, on board or Solutions Module program must be
interrogated. The program should be modified so that only trips defined as User trip are used.
t004
Reserved
4
See diagnosis for t002
t010
Reserved
10
See diagnosis for t002
t019
Reserved
19
See diagnosis for t002
t023
User trip
23
This trip is user defined. The drives internal logic, on board or Solutions module program must be interrogated to find the cause of
this trip. A value of 23 is being written to user trip (Pr
10.38
)
t032
Reserved
32
See diagnosis for t002
t032 to t033
Reserved
32 to 33
See diagnosis for t002
t038 to t039
Reserved
38 to 39
See diagnosis for t002
t040 to t089
User trip
40 to 89
See diagnosis for t023
t099
User trip defined in 2
nd
processor Solutions Module code
99
This solutions module program must be interrogated to find the cause of this trip. A value of 99 is being written to user trip (Pr
10.38
)
t101
User trip
101
See diagnosis for t023
t102 to t111
Reserved
102 to 111
See diagnosis for t002
t112 to t156
User trip
112 to 156
See diagnosis for t023
t161 to t167
Reserved
161 to 167
See diagnosis for t002
t176
Reserved
176
See diagnosis for t002
t192 to t196
Reserved
192 to 196
See diagnosis for t002
t216
User trip
216
See diagnosis for t023
th
Motor thermistor trip
24
Check motor temperature
Check thermistor continuity
Set Pr
7.15
(
in01, 0.81
) = VOLt and reset the drive to disable this function
th.Err
Missing thyristor
173
Hardware fault - return drive to supplier
thS
Motor thermistor short circuit
25
Check motor thermistor wiring
Replace motor / motor thermistor
Set Pr
7.15
(
in01, 0.81
) = VOLt and reset the drive to disable this function
Trip