Installation
15
2.2.3 DIP Switch and Jumper Settings for Remote Sensors
The Liebert XDP is shipped with jumpers and DIP switch settings for normal operation. See
Figure 15
.
Figure 15 DIP switch and jumper settings
Figure 16 Unit-to-unit networking connections
P68
1
3
5
2
4
6
SW2
MICROPROCESSOR AND I/O BOARD
REMOTE T/HSENSOR “A”
REMOTE T/H SENSOR “B”
SW1
SW1
OFF
ON
OFF
ON
Jumper
on 1-2
1
2
3
P78
DIP
Switches
ON
1
3
4
9
10
OFF
2
5
6
7
8
Jumpers
on 1-2, 5-6
OFF ON
1
2
3
4
5
6
7
8
9
10
DIP
Switches
ON
None
OFF
1
2
3
4
5
6
7
8
1
2
3
P78
UNIT DISPLAY
Jumper on 1-2
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
DIP
Switches
ON
1
5
OFF
2
3
4
6
7
8
DIP
Switches
ON
2
5
OFF
1
3
4
6
7
8
SW3
1
2
3
4
5
6
7
8
OFF ON
P3
3 2 1
Jumper
on 2-3
P3
3 2 1
Jumper
on 2-3
302211
Rev. 2
302211
Rev. 2
Termination
Plug
Liebert iCOM
Microprocessor
& I/O Board
Customer
Connection
Points
Crossover
Coupler
Red Crossover
Ethernet Cable
Straight Through
Ethernet Cables
U2U Networking Switch
(Field Supplied)
Unit Display (Rear View)
Not
Used
P64
P66
P64 P66P67
To / From Other
Networked Units
CAN Cable
See Note 1
P6
5
E5
P6
1
P6
3
P11
P13 P7
P12
P67
1. Both cables (P64 and P66) are required.
2. A crossover coupler is provided for unit-to-unit (U2U)
networking. Unplug the red cable from P64 on the
microprocessor and I/O board and connect to one side
of the crossover coupler. The first customer connection
point is to P64 on the microprocessor and I/O board.
The second customer connection point is to the other
side of the crossover coupler. This connects the
microprocessor and I/O board and display to the
private U2U network.
Содержание Liebert XDP
Страница 2: ......