Liebert iCOM Control—Firmware Version XP1.00.010.STD
29
4.3.2 Cooling Module Overview
The Liebert iCOM will display an overview of all connected cooling modules. It does not display a
system view, which would include units other than the cooling modules.
To display an overview of all connected cooling modules:
1. At the default home screen on the Liebert iCOM, press the down arrow. This will display the first
10 modules’ outlet temperature and capacity levels. Press ESC to return to the unit view.
Figure 26 Cooling module overview, first 10 modules
2. Press the down arrow button again to display the next 10 modules’ outlet temperature and
capacity levels.
3. Press ESC to return to the default home screen.
NOTE
The Liebert iCOM control screens display a setting to select a system view, but the Liebert XDP
does not support a system view.
UNIT 1
OFF 9/2013
100%
212°F
Max XD Supply
Air Temp
Liebert XDP
AA01 AA01 AA01 AA01 AA01 AA01 AA01 AA01 AA01AA01
(01) 8/2/2012 08 :33 RST General Alarm
(01) 8/2/2012 08 :20 ACK HIGH CHILLED WATER TEMP
8/4/2012 14 :13:54
ALARM OFF
? for help
for next/previous unit
for system view
ESC
for previous screen
for menu
°F 70 72 74 76 75 73 74 71 77 72
Содержание Liebert XDP
Страница 2: ......