Liebert iCOM Control—Firmware Version XP1.00.010.STD
47
Figure 48 Diagnostics/Service Mode screen, page 1 of 6
Page 1 applies to the Liebert XDC only. No Liebert XDP parameters are present.
Figure 49 Diagnostics/Service Mode screen, page 2 of 6
Manual Mode
—Used to place the Liebert iCOM control in manual mode. This is the initial setting
necessary to activate any of the following items. When the Liebert iCOM is not in manual mode, each
service menu item shows the current status of each parameter.
Pump 1
—Starts the unit’s Pump 1.
Pump 2
—Starts the unit’s Pump 2.
3P Start Active/Complete
—Displays if the startup routine is active, and if it is completed.
3P Actuator Input Request
—Shows the % call for cooling.
3P Actuator Position
—Sets the position of the actuator 0-100% in manual mode.
3P Actuator Open
—Opens the 3P actuator when set to ON in manual mode.
3P Actuator Close
—Closes the 3P actuator when set to ON in manual mode
Valve Feedback
—Opens the valve % in manual mode.
DIAGNOSTICS/SERVICE MODE (page 1 of 6)
UNIT 01
S301
S302
S303
S304
S305
S306
S307
S308
S309
S310
S311
to confirm
for next/previous unit
then
to select parameter
to change parameter
PASSWORD (Actual Level 0)
????
DIAGNOSTICS/SERVICE MODE (page 2 of 6)
UNIT 01
S312
S313
S314
S315
S316
S317
S318
S319
S320
S321
S322
to confirm
for next/previous unit
then
to select parameter
to change parameter
PASSWORD (Actual Level 0)
????
Manual Mode
No
Pump 1
Off
Pump 2
Off
3P Start Completed/Active
No No
3P Actuator Input Request
30.00%
3P Actuator Position
30%
3P Actuator Open
Off
3P Actuator Close
Off
Valve Feedback
30%
Содержание Liebert XDP
Страница 2: ......