Liebert iCOM Control—Firmware Version XP1.00.010.STD
35
Figure 32 Set Alarms screen
High Room Air Temperature
—Sets the threshold where a high room temperature alarm will
occur, based on the actual reading from either remote Sensor A or B. The range for the high room air
temperature alarm is 33.8-95°F (1-35°C); the default is 80.0°F (26.7°C).
Low Room Air Temperature
—Sets the threshold where a low room temperature alarm will occur,
based on the actual reading from either remote Sensor A or B. The range for the high room air
temperature alarm is from 33.8 to 95°F (1 to 35°C); the default is 55.0°F (12.8°C).
High Room Dewpoint
—Sets the threshold where a high room dew point alarm will occur, based on
the calculated values from either remote Sensor A or remote Sensor B. The range for the high room
dew point alarm is from 33.8 to 95°F (1 to 35°C); the default is 65°F (18.3°C).
High Refrigerant Temperature
—Sets the threshold where a high refrigerant temperature alarm
will occur based on the actual reading from the supply refrigerant sensor. The supply refrigerant
temperature is from the Liebert XDP to the modules. The range for the high supply refrigerant
temperature alarm is from 33.8 to 95°F (1 to 35°C); the default is 80°F (26.7°C).
High Chilled Water Temperature
—Sets the threshold where a high chilled water temperature
alarm will occur based on the actual reading from the supply chilled water sensor. The range for the
high chilled water temperature is from 33.8 to 95°F (1 to 35°C); the default is 60°F (15.6°C).
SET ALARMS (page 1 of 1)
to change parameter
to confirm
to select parameter
for next/previous unit
then
UNIT 01
PASSWORD (Actual Level 0)
High Room Air Temperature
Low Room Air Temperature
High Room Dewpoint
High Refrigerant Temperature
High Chilled Water Temperature
????
80.0°F
55.0°F
65.0°F
80.0°F
60.0°F
U201
U202
U203
U204
U205
U206
U207
U208
U209
U210
U211
Содержание Liebert XDP
Страница 2: ......