1.2.1
Components and Features
The FB100 provides the following components and features:
▪
Weather-tight enclosure
▪
Termination printed circuit board (“Termination module”)
▪
32-bit processor print circuit board (“Processor module”)
▪
Battery charger printed circuit board. (“Battery Charger module”)
▪
Backplane printed circuit board
▪
2 MB of field-upgradeable flash ROM (Random Access Memory)
▪
512 KB of battery backed-up RAM (Random Access Memory)
storage
▪
Integral Dual-Variable Sensor (DVS, available on the FB103) for
static pressure and differential pressure measurement using orifice
metering
▪
Pulse Interface module (available on the FloBoss 104) for line
pressure and pulse counts using turbine or rotary metering
▪
Support for a three-wire 100-ohm Resistance Thermal Detector
(RTD) input
▪
Internal lead-acid batteries (optional)
▪
Solar panel mast assembly
▪
Local Operator Interface (LOI) port – EIA-232 (RS-232)
▪
EIA-485 (RS-485) on Comm 1 port
▪
Communications module using EIA-232 (RS-232), EIA-485 (RS-
485), or dial-up modem
▪
Extensive applications firmware
Refer to each component’s Product Data Sheets for the approvals
options for hazardous locations.
Physical
Configuration
Physically, the FB100 consists of a termination module with optional
I/O points, RAM battery backup board, optional Comm 2
communications module, processor module, battery charger module,
backplane, and optional display housed in a compact, weather-tight
case. The FB100 is packaged in a NEMA 4 windowed enclosure that
mounts on a pipestand, to an orifice plate via a 3- or 5-valve manifold,
to a turbine meter, or to a rotary meter. The aluminum alloy enclosure
protects the electronics from physical damage and harsh environments.
Refer to
Figures 1-1