FloBoss 103/104 Instruction Manual
Revised August-2017
Calibration
8-3
1
Close
Shutdn2
L
H
2
Open
L
H
3
Close
L
H
High
Pressure
Remains
Bleed
Bleed
L
H
Operating
Shutdown Sequence
Figure 8-2. Removing the DVS from Service
5.
If you are calibrating a
pressure input
, set up the pressure calibrator
and make the necessary connections to the DVS. Refer to
for the line orientation during the calibration.
Caution
To protect the differential cell of the Dual-Variable Sensor, do not
exceed the differential pressure range on the DVS. Refer to the technical
specifications for the DVS205 (form DVS205, part number D301569X012,
listed in the Additional Technical Information section in Chapter 1.
L
H
diff.dsf
Differential Pressure
static.dsf
L
H
Static Pressure
Figure 8-3. Pressure Calibration Open/Close Orientation
6.
If you are calibrating a
temperature input
, disconnect the RTD
sensor and connect a decade box (or comparable equipment) to the
RTD terminals of the FB100.
7.
Click
Calibrate
under the desired input to calibrate Diff Press, Stat
Press, or Temperature. The Set Zero calibration window displays.
C
l
o
s
e
d
C
l
o
s
e
d
C
l
o
s
e
d
C
l
o
s
e
d
O
p
e
n
C
l
o
s
e
d