DVC6000f Digital Valve Controllers
December 2009
4-110
Table 4-39. Input Selector Function Block Parameter Definitions (Continued)
Label
PARAMETER_NAME
Description
Initial
Value
Range
Block
Mode
RO /
RW
Index
Number
Input 2
IN_2
12
ALL
Status
BAD
NC
constant
Data Type: DS-65
The block input value and status.
Value
0
Input 3
IN_3
13
ALL
Status
BAD
NC
constant
Data Type: DS-65
The block input value and status.
Value
0
Input 4
IN_4
14
ALL
Status
BAD
NC
constant
Data Type: DS-65
The block input value and status.
Value
0
Disable Analog Input 1
DISABLE_1
15
ALL
Status
BAD
NC
constant
Data Type: DS-66
Enable/Disable for Input_1, If parameter is TRUE
then input is disabled. If parameter status is BAD it is
not evaluated.
Value
0=Use
1=Disable
0
Disable Analog Input 2
DISABLE_2
16
ALL
Status
BAD
NC
constant
Data Type: DS-66
Enable/Disable for Input_2, If parameter is TRUE
then input is disabled. If parameter status is BAD it is
not evaluated.
Value
0=Use
1=Disable
0
Disable Analog Input 3
DISABLE_3
17
ALL
Status
BAD
NC
constant
Data Type: DS-66
Enable/Disable for Input_3, If parameter is TRUE
then input is disabled. If parameter status is BAD it is
not evaluated.
Value
0=Use
1=Disable
0
Disable Analog Input 4
DISABLE_4
18
ALL
Status
BAD
NC
constant
Data Type: DS-66
Enable/Disable for Input_4, If parameter is TRUE
then input is disabled. If parameter status is BAD it is
not evaluated.
Value
0=Use
1=Disable
0
Select Type
SELECT_TYPE
19
ALL
1=First Good
2=Minimum
3=Maximum
4=Middle
5=Average
6=Hot Spare
0
Data Type: Unsigned8
Determines the selector action
Min Good
MIN_GOOD
20
ALL
1
−
4
0 initial value only
0
Data Type: Unsigned8
The minimum number of inputs which are “good” is
less than the value of MIN_GOOD then set the OUT
status to “bad”.
Selected
SELECTED
21
RO
N/A
Status
Data Type: DS-66
The integer indicating the selected input number.
Value
0
−
8
Dynamic
Operator Select
OP_SELECT
22
ALL
Status
BAD
NC
constant
Data Type: DS-66
An operator settable parameter to force a given input
to be used.
Value
0
−
8
0
−
Continued
−
4
Содержание Fisher FIELDVUE DVC6000f
Страница 54: ...DVC6000f Digital Valve Controllers December 2009 2 30 2 ...
Страница 62: ...DVC6000f Digital Valve Controllers December 2009 4 2 4 ...
Страница 127: ...Transducer Block December 2009 4 67 4 ...
Страница 141: ...AO Function Block December 2009 4 81 4 ...
Страница 207: ...MAI Function Block December 2009 4 147 4 ...
Страница 219: ...DO Function Block December 2009 4 159 4 ...
Страница 231: ...DI Function Block December 2009 4 171 4 ...
Страница 232: ...DVC6000f Digital Valve Controllers December 2009 4 172 Block Parameter Index 4 173 Block Channel Index 4 186 4 ...
Страница 302: ...DVC6000f Digital Valve Controllers December 2009 8 16 8 ...
Страница 303: ...Principle of Operation December 2009 A 1 A A Appendix A Principle of Operation Digital Valve Controller Operation A 2 A ...
Страница 306: ...DVC6000f Digital Valve Controllers December 2009 A 4 A ...
Страница 350: ...DVC6000f Digital Valve Controllers December 2009 E 6 E ...
Страница 368: ...DVC6000f Digital Valve Controllers December 2009 F 18 F ...
Страница 372: ...DVC6000f Digital Valve Controllers December 2009 Glossary 4 Notes G Glossary ...
Страница 382: ...DVC6000f Digital Valve Controllers December 2009 Index 10 F Index ...
Страница 383: ...This page intentionally left blank ...