DVC6000f Digital Valve Controllers
December 2009
2-4
In addition to remote venting of the
unit, ensure that all caps and covers
are correctly installed. Failure to do so
could result in personal injury or
property damage from fire or
explosion, and area re-classification.
Special Instructions for “Safe Use” and
Installation in Hazardous Locations
Certain nameplates may carry more than one
approval, and each approval may have unique
installation/wiring requirements and/or conditions of
“safe use”. These special instructions for “safe use”
are in addition to, and may override, the standard
installation procedures. Special instructions are listed
by approval.
WARNING
Failure to follow these conditions of
safe use could result in personal
injury or property damage from fire or
explosion, and area re-classification.
CSA
Special Conditions of Safe Use
Intrinsically Safe and FISCO, Explosion proof,
Division 2, Dust-Ignition proof
No special conditions for safe use.
Refer to table 1-3 for approval information, figures B-1
and B-4 for CSA loop schematics, and figures B-3 and
B-5 for the CSA nameplates.
FM
Special Conditions of Safe Use
Intrinsically Safe and FISCO, Explosion proof,
Non-incendive, Dust-Ignition proof
Refer to table 1-4 for approval information, figures B-6
and B-9 for FM loop schematics, and figures B-8 and
B-10 for the FM nameplates.
ATEX
Special Conditions for Safe Use
Intrinsically Safe, Dust
DVC6010f, DVC6020f, DVC6030f, and DVC6005f
1. This apparatus can only be connected to an
intrinsically safe certified equipment and this
combination must be compatible as regards the
intrinsically safe rules.
2. The FISCO electrical parameters of this equipment
must not exceed any following values:
U
O
v
17.5 V; I
O
v
380 mA; P
O
v
5.32 W
3. Operating ambient temperature:
−
52
C or
−
40
C
to + 85
C
4. For the model with aluminum body: the apparatus
must not be submitted to frictions or mechanical
impacts.
DVC6015, DVC6025, and DVC6035
1. This apparatus can only be connected to an
intrinsically safe certified equipment and this
combination must be compatible as regards the
intrinsically safe rules.
Refer to table 1-5 for additional approval information,
and figure B-11 for the the ATEX Intrinsic Safety, Dust
nameplates.
Flameproof, Dust
DVC6010f, DVC6020f, and DVC6030f
Operating ambient temperature:
−
52
C or
−
40
C to
+ 85
C
DVC6005f, DVC6015, DVC6025, and DVC6035
Operating ambient temperature as indicated on the
nameplate.
Refer to table 1-5 for additional approval information,
and figure B-12 for the ATEX Flameproof, Dust
nameplates.
Type n, Dust
DVC6010f, DVC6020f, and DVC6030f
Operating ambient temperature:
−
52
C or
−
40
C to
+ 80
C
DVC6005f, DVC6015, DVC6025, and DVC6035
Operating ambient temperature as indicated on the
nameplate.
Refer to table 1-5 for additional approval information,
and figure B-13 for the ATEX Type n, Dust
nameplates.
2
Содержание Fisher FIELDVUE DVC6000f
Страница 54: ...DVC6000f Digital Valve Controllers December 2009 2 30 2 ...
Страница 62: ...DVC6000f Digital Valve Controllers December 2009 4 2 4 ...
Страница 127: ...Transducer Block December 2009 4 67 4 ...
Страница 141: ...AO Function Block December 2009 4 81 4 ...
Страница 207: ...MAI Function Block December 2009 4 147 4 ...
Страница 219: ...DO Function Block December 2009 4 159 4 ...
Страница 231: ...DI Function Block December 2009 4 171 4 ...
Страница 232: ...DVC6000f Digital Valve Controllers December 2009 4 172 Block Parameter Index 4 173 Block Channel Index 4 186 4 ...
Страница 302: ...DVC6000f Digital Valve Controllers December 2009 8 16 8 ...
Страница 303: ...Principle of Operation December 2009 A 1 A A Appendix A Principle of Operation Digital Valve Controller Operation A 2 A ...
Страница 306: ...DVC6000f Digital Valve Controllers December 2009 A 4 A ...
Страница 350: ...DVC6000f Digital Valve Controllers December 2009 E 6 E ...
Страница 368: ...DVC6000f Digital Valve Controllers December 2009 F 18 F ...
Страница 372: ...DVC6000f Digital Valve Controllers December 2009 Glossary 4 Notes G Glossary ...
Страница 382: ...DVC6000f Digital Valve Controllers December 2009 Index 10 F Index ...
Страница 383: ...This page intentionally left blank ...