Table 4-31. PID Function Block System Parameters Definitions (Continued)
Label
PARAMETER_NAME
Description
Initial Value
Range
Block
Mode
RO /
RW
Index
Number
Deviation High Priority
DV_HI_PRI
56
ALL
0 to 15
0
Data Type: Unsigned8
The priority of the deviation high alarm.
Deviation High Limit
DV_HI_LIM
57
ALL
PV_SCALE, or +INF
+INF
Data Type: Float
The setting for the alarm limit used to detect the
deviation high alarm condition.
Deviation Low Priority
DV_LO_PRI
58
ALL
0 to 15
0
Data Type: Unsigned8
The priority of the deviation low alarm.
Deviation Low Limit
DV_LO_LIM
59
ALL
−
INF, or
−
PV span to 0
−
INF
Data Type: Float
The setting for the alarm limit use to detect the
deviation low alarm condition.
High High Alarm
HI_HI_ALM
60
Data Type: DS-71
The HI HI alarm data, which includes a value of
the alarm, a timestamp of occurrence, and the
state of the alarm.
VALUE Data Type: Float
UNACKNOWLEDGED
60.1
RW
N/A
0=Undefined
1=Acknowledged
2=
Unacknowledged
0=undefined
ALARM_STATE
60.2
RO
N/A
0=Undefined
1=Clear reported
2=Clear not reported
3=Active reported
4=Active not reported
0=undefined
TIME_STAMP
60.3
RO
N/A
0
SUBCODE
60.4
RO
N/A
0
VALUE
60.5
RO
N/A
0
High Alarm
HI_ALM
61
Data Type: DS-71
The HI alarm data, which includes a value of the
alarm, a timestamp of occurrence, and the state
of the alarm.
VALUE Data Type: Float
UNACKNOWLEDGED
61.1
RW
N/A
0=Undefined
1=Acknowledged
2=
Unacknowledged
0=undefined
ALARM_STATE
61.2
RO
N/A
0=Undefined
1=Clear reported
2=Clear not reported
3=Active reported
4=Active not reported
0=undefined
TIME_STAMP
61.3
RO
N/A
0
SUBCODE
61.4
RO
N/A
0
VALUE
61.5
RO
N/A
0
Low Alarm
LO_ALM
62
Data Type: DS-71
The LO alarm data, which includes a value of the
alarm, a timestamp of occurrence, and the state
of the alarm.
VALUE Data Type: Float
UNACKNOWLEDGED
62.1
RW
N/A
0=Undefined
1=Acknowledged
2=
Unacknowledged
0=undefined
ALARM_STATE
62.2
RO
N/A
0=Undefined
1=Clear reported
2=Clear not reported
3=Active reported
4=Active not reported
0=undefined
TIME_STAMP
62.3
RO
N/A
0
SUBCODE
62.4
RO
N/A
0
VALUE
62.5
RO
N/A
0
Low Low Alarm
LO_LO_ALM
63
Data Type: DS-71
The LO LO alarm data, which includes a value of
the alarm, a timestamp of occurrence, and the
state of the alarm.
VALUE Data Type: Float
UNACKNOWLEDGED
63.1
RW
N/A
0=Undefined
1=Acknowledged
2=
Unacknowledged
0=undefined
ALARM_STATE
63.2
RO
N/A
0=Undefined
1=Clear reported
2=Clear not reported
3=Active reported
4=Active not reported
0=undefined
TIME_STAMP
63.3
RO
N/A
0
SUBCODE
63.4
RO
N/A
0
VALUE
63.5
RO
N/A
0
−
Continued
−
4
Содержание Fisher FIELDVUE DVC6000f
Страница 54: ...DVC6000f Digital Valve Controllers December 2009 2 30 2 ...
Страница 62: ...DVC6000f Digital Valve Controllers December 2009 4 2 4 ...
Страница 127: ...Transducer Block December 2009 4 67 4 ...
Страница 141: ...AO Function Block December 2009 4 81 4 ...
Страница 207: ...MAI Function Block December 2009 4 147 4 ...
Страница 219: ...DO Function Block December 2009 4 159 4 ...
Страница 231: ...DI Function Block December 2009 4 171 4 ...
Страница 232: ...DVC6000f Digital Valve Controllers December 2009 4 172 Block Parameter Index 4 173 Block Channel Index 4 186 4 ...
Страница 302: ...DVC6000f Digital Valve Controllers December 2009 8 16 8 ...
Страница 303: ...Principle of Operation December 2009 A 1 A A Appendix A Principle of Operation Digital Valve Controller Operation A 2 A ...
Страница 306: ...DVC6000f Digital Valve Controllers December 2009 A 4 A ...
Страница 350: ...DVC6000f Digital Valve Controllers December 2009 E 6 E ...
Страница 368: ...DVC6000f Digital Valve Controllers December 2009 F 18 F ...
Страница 372: ...DVC6000f Digital Valve Controllers December 2009 Glossary 4 Notes G Glossary ...
Страница 382: ...DVC6000f Digital Valve Controllers December 2009 Index 10 F Index ...
Страница 383: ...This page intentionally left blank ...