DVC6000f Digital Valve Controllers
December 2009
4-52
Table 4-13. Transducer Block Parameter Definitions (Continued)
Label
PARAMETER_NAME
Description
Protect
Category
Initial Value
Range
Mode
RO /
RW
Index
Number
Advise Active
ADVISE_ACTIVE
61
RO
(1)
N/A
0: Drive Current
1: Drive Signal
2: Processor Impaired
3: Output Block Timeout
4: Blocks Set to Defaults
5: Travel Sensor
6: Outlet Pressure
Sensor
7: Supply Pressure
Sensor
8: Temperature Sensor
9: Supply Pressure
10: Temperature Limit
11: Travel Deviation
12: Travel Limit
13: Travel Accumulator
14: Cycle Counter
15: Performance Critical
16: Performance
Reduced
17: Performance
Information
18: Shutdown Alert
All bits: 0
N/A
Data Type: Bit String (4 byte)
0=inactive
1=active
Advise Alert Status
Failed Enable
FAILED_ENABLE
62
RW
ALL
Same as for
FAILED_ACTIVE above
Enabled Bits:
0: Drive Current
2: Processor
Impaired
4: Blocks Set to
Default
5: Travel Sensor
15: Performance
Critical
18: Shutdown
Alert
ALL
Data Type: Bit String (4 byte)
0=disable
1=enable
Failed alert enable. Enable allows
detection of alert. All alerts can be
disabled.
Maintenance Enable
MAINT_ENABLE
63
RW
ALL
Same as for
MAINT_ACTIVE above
Enabled Bits:
1: Drive Signal
3: Output Block
Timeout
6: Outlet Pressure
Sensor
9: Supply
Pressure
11: Travel
Deviation
13: Travel
Accumulator
14: Cycle Counter
16: Performance
Reduced
ALL
Data Type: Bit String (4 byte)
0=disable
1=enable
Maintenance alert enable. Enable
allows detection of alert. All alerts
can be disabled.
Advise Enable
ADVISE_ENABLE
64
RW
ALL
Same as for
ADVISE_ENABLE above
Enabled Bits:
8: Temperature
Sensor
9: Supply
Pressure Sensor
10: Temperature
Limit
12: Travel Limit
ALL
Data Type: Bit String (4 byte)
0=disable
1=enable
Advise alert enable. Enable allows
detection of alert. All alerts can be
disabled.
Failed Suppress
FAILED_MASK
65
RW
ALL
Same as for
FAILED_ACTIVE above
All bits: 0
ALL
Data Type: Bit String (4 byte)
0=disable
1=enable
Failed alert mask. MASK controls
whether an alert is reported. If alert
is enabled the alert condition is
evaluated and the ACTIVE
parameter is updated to reflect if
alert is active or not. If the bit is set
reporting is suppressed. Default is
all bits cleared.
1. These parameters can be written when PWA_SIMULATE is active and Protect Category is not ALL.
−
Continued
−
4
Содержание Fisher FIELDVUE DVC6000f
Страница 54: ...DVC6000f Digital Valve Controllers December 2009 2 30 2 ...
Страница 62: ...DVC6000f Digital Valve Controllers December 2009 4 2 4 ...
Страница 127: ...Transducer Block December 2009 4 67 4 ...
Страница 141: ...AO Function Block December 2009 4 81 4 ...
Страница 207: ...MAI Function Block December 2009 4 147 4 ...
Страница 219: ...DO Function Block December 2009 4 159 4 ...
Страница 231: ...DI Function Block December 2009 4 171 4 ...
Страница 232: ...DVC6000f Digital Valve Controllers December 2009 4 172 Block Parameter Index 4 173 Block Channel Index 4 186 4 ...
Страница 302: ...DVC6000f Digital Valve Controllers December 2009 8 16 8 ...
Страница 303: ...Principle of Operation December 2009 A 1 A A Appendix A Principle of Operation Digital Valve Controller Operation A 2 A ...
Страница 306: ...DVC6000f Digital Valve Controllers December 2009 A 4 A ...
Страница 350: ...DVC6000f Digital Valve Controllers December 2009 E 6 E ...
Страница 368: ...DVC6000f Digital Valve Controllers December 2009 F 18 F ...
Страница 372: ...DVC6000f Digital Valve Controllers December 2009 Glossary 4 Notes G Glossary ...
Страница 382: ...DVC6000f Digital Valve Controllers December 2009 Index 10 F Index ...
Страница 383: ...This page intentionally left blank ...