AO Function Block
December 2009
4-77
Table 4-24. Analog Output Function Block Parameter Definitions (Continued)
Label
PARAMETER_NAME
Description
Initial
Value
Range
Block
Mode
RO /
RW
Index
Number
Setpoint Rate Down
SP_RATE_DN
18
ALL
Positive, 0 disables
rate limiting PV units
+INF
Data Type: Float
Ramp rate for downward set point changes.
When the ramp rate is set to zero, the set point is
used immediately.
Setpoint Rate Up
SP_RATE_UP
19
ALL
Positive, 0 disables
rate limiting PV units
+INF
Data Type: Float
Ramp rate for upward set point changes. When
the ramp rate is set to zero, the setpoint is used
immediately.
Setpoint High Limit
SP_HI_LIM
20
ALL
PV Scale +/
−
10%
100
Data Type: Float
The highest set point value allowed. SP_HI_LIM
must be greater than SP_LO_LIM.
Setpoint Low Limit
SP_LO_LIM
21
ALL
PV Scale +/
−
10%
0
Data Type: Float
The lowest set point value allowed. SP_LO_LIM
must be less than SP_HI_LIM.
AO Channel
CHANNEL
22
OOS
1=Setpoint
1=Setpoint
Data Type: Unsigned16
Defines which transducer parameter receives the
AO output. Select Setpoint to control valve
position.
Fault State Time
FSTATE_TIME
23
ALL
Positive, seconds
0
Data Type: Float
Time from failure detection to reaction if failure
still exists.
Fault State Value
FSTATE_VAL
24
ALL
PV Scale +/
−
10%
0
Data Type: Float
Preset value to use if I/O_OPTS Fault State to
Value or Use Fault State Value on Restart is set.
Back Calculation Output
BKCAL_OUT
25
RO
N/A
Status Limits
Dynamic
Data Type: DS-65
The value and status required by the BKCAL_IN
input of another block to prevent reset windup
and to provide bumpless transfer to closed loop
control.
Value
Remote Cascade Input
RCAS_IN
26
ALL
Status
BAD:
NoCom:
NoVal:
const
Data Type: DS-65
Target SP and status by supervisory host
Value
0 Trk
Shed Options
SHED_OPT
27
ALL
Defined by FF spec
0=Invalid
1=Normal Shed,
Normal Return
2=Normal Shed, No
Return
3=Shed to Auto,
normal return
4=Shed to Auto, no
return. Target mode
changes to Auto on
detection of a shed
condition
5=Shed to Manual,
normal return
6=Shed to Manual,
No return. Target
mode changes to
MAN on detection of
a shed condition.
7=Shed to retained
target, normal return
8=Shed to retained
target, no return.
(Change target to
retained target)
0
Data Type: Unsigned8
Defines the action to be taken when the set point
is not updated in a remote mode.
Remote Cascade Output
RCAS_OUT
28
RO
N/A
Status
Dynamic
Data Type: DS-65
Block set point and status after ramping
Value
−
Continued
−
4
Содержание Fisher FIELDVUE DVC6000f
Страница 54: ...DVC6000f Digital Valve Controllers December 2009 2 30 2 ...
Страница 62: ...DVC6000f Digital Valve Controllers December 2009 4 2 4 ...
Страница 127: ...Transducer Block December 2009 4 67 4 ...
Страница 141: ...AO Function Block December 2009 4 81 4 ...
Страница 207: ...MAI Function Block December 2009 4 147 4 ...
Страница 219: ...DO Function Block December 2009 4 159 4 ...
Страница 231: ...DI Function Block December 2009 4 171 4 ...
Страница 232: ...DVC6000f Digital Valve Controllers December 2009 4 172 Block Parameter Index 4 173 Block Channel Index 4 186 4 ...
Страница 302: ...DVC6000f Digital Valve Controllers December 2009 8 16 8 ...
Страница 303: ...Principle of Operation December 2009 A 1 A A Appendix A Principle of Operation Digital Valve Controller Operation A 2 A ...
Страница 306: ...DVC6000f Digital Valve Controllers December 2009 A 4 A ...
Страница 350: ...DVC6000f Digital Valve Controllers December 2009 E 6 E ...
Страница 368: ...DVC6000f Digital Valve Controllers December 2009 F 18 F ...
Страница 372: ...DVC6000f Digital Valve Controllers December 2009 Glossary 4 Notes G Glossary ...
Страница 382: ...DVC6000f Digital Valve Controllers December 2009 Index 10 F Index ...
Страница 383: ...This page intentionally left blank ...