DVC6000f Digital Valve Controllers
December 2009
3-2
Basic Setup
WARNING
Changes to the instrument setup may
cause changes in the output pressure
or valve travel. Depending on the
application, these changes may upset
process control, which may result in
personal injury or property damage.
When the DVC6000f digital valve controller is ordered
as part of a control valve assembly, the factory
mounts the digital valve controller and sets up the
instrument as specified on the order. When mounting
to a valve in the field, the instrument needs to be
setup to match the instrument to the valve and
actuator.
Before beginning basic setup, be sure the instrument
is correctly mounted as described in the Installation
section.
Basic Setup includes the following procedures:
Device Setup
Auto Travel Calibrate
Performance Tuner (Optional)
Note
The DVC6000f may keep the
Transducer Block Mode
Out-of-Service if the instrument is
not properly mounted.
To setup and calibrate the
instrument, the Transducer Block
Mode must be Manual, and the
Protection must be None.
When using DD methods the
method will request that you
change the mode, but make
changes in Protection
automatically.
Table 3-1. Factory Default Settings
Setup Parameter
Default Setting
Travel Cutoff Hi
Travel Cutoff Lo
Travel Integral Gain
Travel Calibration Trigger
99.5%
0.5%
9.4 repeats/min
No
Travel Integral Enable
Travel Integral Limit Hi
Travel Integral Limit Lo
Travel Integral Deadzone
On
30%
−
30%
0.25%
Pressure Cutoff Hi
Pressure Cutoff Lo
Pressure Integral Deadzone
Pressure Integral Hi Limit
Pressure Integral Lo Limit
99.5%
−
0.5%
0.25%
50.0%
−
50.0%
Input Characterization
Shutdown Trigger
Shutdown Recovery
Output Block Timeout
Linear
All Off
All Auto Recovery
600 sec
If you have a host system that
overrides transducer block
parameters ensure that the Protection
setting is not left as None. Doing so
will result in transducer block
parameters being overwritten.
Transducer Block Mode
(TB
>
Configure/Setup
>
Detailed Setup
>
Transducer
Block Mode)
To setup and calibrate the instrument, the transducer
block mode must be in Manual. For more information
about transducer block mode, refer to page 4-21.
Protection
(TB
>
Configure/Setup
>
Detailed Setup
>
Protection)
To setup and calibrate the instrument, the protection
must be set to None with the Field Communicator. For
more information about configuration protection refer
to page 4-21.
Device Setup
(TB
>
Configure/Setup
>
Basic Setup
>
Device Setup)
To have the Field Communicator automatically setup
the instrument using specified actuator information,
from the Menu select Transducer Block,
Configure/Setup, Basic Setup, and Device Setup.
Follow the prompts on the Field Communicator display
to setup the instrument. Table 3-2 provides the
actuator information required to setup and calibrate
the instrument.
3
Содержание Fisher FIELDVUE DVC6000f
Страница 54: ...DVC6000f Digital Valve Controllers December 2009 2 30 2 ...
Страница 62: ...DVC6000f Digital Valve Controllers December 2009 4 2 4 ...
Страница 127: ...Transducer Block December 2009 4 67 4 ...
Страница 141: ...AO Function Block December 2009 4 81 4 ...
Страница 207: ...MAI Function Block December 2009 4 147 4 ...
Страница 219: ...DO Function Block December 2009 4 159 4 ...
Страница 231: ...DI Function Block December 2009 4 171 4 ...
Страница 232: ...DVC6000f Digital Valve Controllers December 2009 4 172 Block Parameter Index 4 173 Block Channel Index 4 186 4 ...
Страница 302: ...DVC6000f Digital Valve Controllers December 2009 8 16 8 ...
Страница 303: ...Principle of Operation December 2009 A 1 A A Appendix A Principle of Operation Digital Valve Controller Operation A 2 A ...
Страница 306: ...DVC6000f Digital Valve Controllers December 2009 A 4 A ...
Страница 350: ...DVC6000f Digital Valve Controllers December 2009 E 6 E ...
Страница 368: ...DVC6000f Digital Valve Controllers December 2009 F 18 F ...
Страница 372: ...DVC6000f Digital Valve Controllers December 2009 Glossary 4 Notes G Glossary ...
Страница 382: ...DVC6000f Digital Valve Controllers December 2009 Index 10 F Index ...
Страница 383: ...This page intentionally left blank ...