![Emerson Fisher 4660 Скачать руководство пользователя страница 4](http://html.mh-extra.com/html/emerson/fisher-4660/fisher-4660_instruction-manual_102283004.webp)
Instruction Manual
D200163X012
4660 Pressure Pilot
June 2017
4
Table 1. Specifications (continued)
Safety Instrumented System Classification
SIL3 capable certified by exida Consulting LLC
Approximate Weight
2.3 kg (5 pounds)
Options
Visual output indication,
stainless steel panel
mounting flange,
set point indication,
tamper‐resistant front cover
Declaration of SEP
Fisher Controls International LLC declares this
product to be in compliance with Article 4 paragraph
3 of the PED Directive 2014/68/EU. It was designed
and manufactured in accordance with Sound
Engineering Practice (SEP) and cannot bear the CE
marking related to PED compliance.
However, the product
may
bear the CE marking to
indicate compliance with
other
applicable European
Community Directives.
NOTE: Specialized instrument terms are defined in ANSI/ISA Standard 51.1 -
Process Instrument Terminology.
1. The pressure and temperature limits in this document and any applicable standard or code limitation should not be exceeded.
2. Normal m
3
/hr—normal cubic meters per hour (0
C and 1.01325 bar absolute). Scfh—standard cubic feet per hour (60
F and 14.7 psia).
3. Supply pressure at 2.1 bar (30 psig).
Table 2. Additional Specifications, Bar
BOURDON TUBE RATING
(1)
SET RANGE
(1)
SET POINT
D
P
MIN
(MINIMUM ALLOWABLE DIFFERENCE
BETWEEN HIGH AND LOW SETTINGS)
TRIP‐TO‐RESET ZONE
Single High‐
Low Unit
High‐Only/
Low‐Only Pair
6.9
17.2
34.5
69.0
0.3 to 6.6
0.6 to 16.6
1.1 to 33.4
2.1 to 67.9
0.7
1.7
3.5
6.9
0.3
0.6
1.1
2.1
0.2
0.3
0.6
1.1
103.4
172.4
344.8
517.2
689.5
(2)
3.2 to 100.2
5.2 to 167.2
10.4 to 334.4
15.6 to 501.5
20.7 to 668.8
10.4
17.3
34.5
51.8
103.4
3.2
5.2
10.4
15.6
20.7
1.6
2.6
5.2
7.8
10.3
1. Rating indicated on Bourdon tube and set range on front panel are in kPa (1 bar = 100 kPa).
2. NACE compliant material only.
Table 3. Additional Specifications, Psig
BOURDON TUBE
RATING
SET RANGE
SET POINT
D
P
MIN
(MINIMUM ALLOWABLE DIFFERENCE
BETWEEN HIGH AND LOW SETTINGS)
TRIP‐TO‐RESET ZONE
Single High‐
Low Unit
High‐Only/
Low‐Only Pair
100
250
500
1000
3 to 97
8 to 242
15 to 485
30 to 970
10
25
50
100
3.0
7.5
15.0
30.0
1.5
3.8
7.5
15.0
1500
2500
5000
7500
10,000
(1)
45 to 1455
75 to 2425
150 to 4850
225 to 7275
300 to 9700
150
250
750
1025
1500
45
75
150
225
300
23
38
75
113
150
1. NACE compliant material only.