4660 Pressure Pilot
June 2017
12
6. Connect an external pressure source to the process pressure connection. This external pressure source should be a
regulated air or gas supply that is adjustable to zero. The external pressure source must be capable of supplying a
process pressure that will be equal to or greater than the desired high set point pressure.
7. Continue with the appropriate procedures described below. Replace the cover and cover screws after all
adjustments are completed.
Setting the High Set Point
Note
To ensure that full output pressure will be indicated during the following steps, make sure the first six steps of the Preliminary
Adjustments procedure have been completed before proceeding.
WARNING
To avoid personal injury or property damage caused by a sudden release of pressure, do not exceed the Bourdon Tube
rating (see tables 2 and 3).
To set the high set point pressure, perform the following four steps:
1. Adjust the external pressure source to the desired high set point pressure.
2. Check that full output pressure is being registered by using a pressure gauge installed in the output pressure line or
by using the optional output indicator (key 88). The optional output indicator shows a green color when the output
pressure is at full pressure and black when the output pressure is at zero.
3. Slowly turn the HIGH SET knob counterclockwise until the desired high set point is obtained. The high set point is
obtained when the output pressure of the pilot has changed from full output to zero.
4. Lock the locking disc (key 69).
Setting the Low Set Point
Note
To ensure that full output pressure will be indicated during the following steps:
Make sure that the first six steps of the Preliminary Adjustments procedure found on page 11 have been completed before
proceeding, and
Make sure the difference between the high set point pressure and the low set point pressure is greater than or equal to the
appropriate Set Point
D
P
MIN
value specified in tables 2 and 3.
To set the low set point pressure, perform the following four steps:
1. Adjust the external pressure source to the desired low set point pressure.
2. Check that full output pressure is being registered by using a pressure gauge installed in the output pressure line or
by using the optional output indicator (key 88). The optional output indicator shows a green color when the output
pressure is at full pressure and black when the output pressure is at zero.