MODBUS
The RS485 Network and Hardware Setup
•
6
-
11
The Comfort Alert diagnostic alarms are configurable
in the E2 as Disabled, Failure, Alarm, or Notice with an
accompanying priority setting. All Comfort Alert codes
will share the same advisory type and priority parameters.
High/Low Occ/Unocc Space Temperature Alarms
The thermostat does not provide alarming information
on either high or low temperatures for the Space tempera-
ture sensor. Therefore, the E2 application will provide this
functionality.
Supply Sensor Fail Alarm
The thermostat does not provide alarm information on
a failure of the supply temperature probe (if installed). The
E2 application will provide this functionality. Advisory
type, priority, and delay is provided for the supply sensor
fail advisory.
Conditions for Return to Normal (RTN) on Diag-
nostic Codes
The E2 application will issue an RTN on an active
advisory when the corresponding bit of the diagnostic
code goes to zero. If multiple diagnostic advisories are
active simultaneously, they will all return to normal when
the code reads zero.
6.3.10 Refrigerant Leak Detection
System (RLDS)
The RLDS provides for the continuous monitoring of
refrigerant gas levels in up to 16 separate test zones or
channels. The instrument is programmed to monitor a
variety of gases and independent leak (small), spill
(medium), and evacuation (large) levels may be desig-
nated for each zone. The instrument also retains a log of
previous readings that can be accessed for analysis.
Figure 6-9
- RLDS
The RLDS has alarm level configuration parameters
that are synchronized. These will be read first from the
device. The E2 will be master of all other parameters. An
audible alarm and front panel indicators are provided to
signal alarm and fault conditions, and relay contacts are
provided that can be used to trigger external alarm devices
in the event of a system fault, or if a leak (small), spill
(medium), or evacuation (large) level of gas is detected.
The system also may be fitted with an optional two-chan-
nel 4-20mA current loop board for connection to remote
monitoring equipment.
Welded Contactor
Compressor always runs.
• Compressor contactor has failed closed
• Thermostat demand signal is not connected
to module.
Welded Contactor
Low Voltage
Control circuit < 17VAC.
• Control circuit transformer is overloaded
• Low line voltage (contact utility if voltage
at disconnect is low)
Compressor Low Volt Trip
Protector Trip
Thermostat demand signal Y is
present, but the compressor is
not running.
• Compressor protector is open.
• Outdoor unit power disconnect is open.
• Compressor circuit breaker or fuse(s) is
open.
• Broken wire or connector is not making
contact.
• High pressure switch open if present in
system.
• Compressor contactor has failed open.
Protector Trip
Comfort Alert
Descriptions
Cause
E2 Advisory
Table 6-6
-Comfort Alert Outputs
Содержание E2
Страница 2: ......
Страница 4: ......
Страница 16: ......
Страница 24: ......
Страница 48: ......
Страница 55: ......
Страница 56: ......
Страница 72: ...6 16 E2 RX BX CX I O Manual 026 1614 Rev 4 5 JAN 2013 ...
Страница 75: ...BACnet The RS485 Network and Hardware Setup 6 19 ...
Страница 79: ...BACnet The RS485 Network and Hardware Setup 6 23 ...
Страница 80: ...6 24 E2 RX BX CX I O Manual 026 1614 Rev 4 5 JAN 2013 ...
Страница 81: ......
Страница 82: ......
Страница 92: ...8 6 E2 RX BX CX I O Manual 026 1614 Rev 4 5 JAN 2013 ...
Страница 94: ...8 8 E2 RX BX CX I O Manual 026 1614 Rev 4 5 JAN 2013 ...
Страница 114: ......
Страница 144: ......
Страница 203: ......
Страница 204: ......
Страница 226: ......
Страница 253: ......
Страница 254: ......
Страница 257: ......
Страница 258: ......
Страница 267: ......
Страница 268: ......
Страница 270: ......
Страница 282: ......