11.6.11 Separate Setpoints
The Separate Setpoints strategy for AHU allows a Cut
In/Cut Out setpoint to be set up for
each
heat and cool
stage instead of just one cool and one heat setpoint set up
for each stage (Normal strategy). Dehumidification con-
trol can be performed while controlling with separate set-
points.
11.6.12 AHU Zone Control
Unlike MultiFlex RTU rooftop controller applications,
AHU applications are not required to be grouped into
Zone applications (AHUs are usually large enough to be
“zones” in and of themselves).
However, if desired, you may associate an AHU Con-
trol application with a Zone application. The AHU will
then use the Zone’s Temperature Control setpoints, occu-
pancy state, summer/winter state, and economization and
dehumidification enable signals. More information on
Zone control is available in
Section 11.7, Zone Control
.
11.6.13 Hardware Overview
To set up an AHU for control by an E2, numerous tem-
perature and humidity sensors for several different appli-
cations must be connected to the I/O Network, as well as
fan and cool proof checking devices, economization
checking devices, curtailment devices, and all of the heat-
ing, cooling, and dehumidification outputs.
Listed below are wiring instructions for some of the
inputs and outputs that are part of a typical AHU setup.
Table 11-10
- Suction Group Inputs
Inputs
Sensor Type
Wiring
Instructions
Space Temperature
Temperature
See Table 9-1 on
page 9-3
Space Humidity
Humidity
See Table 9-1 on
page 9-3
Supply Air Temp
Temperature
See Table 9-1 on
page 9-3
Return Air Temp
Temperature
See Table 9-1 on
page 9-3
Outdoor Air Temp
Temperature
Set up as Out-
door Air Provider
in Global Data
(see
Section
10.17
).
Outdoor Air Humid
Humidity
Set up as Out-
door Humidity
Provider in
Global Data (see
Section 10.17
).
Curtailment Device
Digital
Set up as Curtail-
ment in Global
Data (see
Sec-
tion 10.17
).
Fan Proof
Digital
See Table 9-1 on
page 9-3
Fan Proof Reset
Digital
See Table 9-1 on
page 9-3
VS Inverter Alarm
Digital
See Table 9-1 on
page 9-3
Enthalpy Switch
(Indoor and/or Out-
door)
Digital
See Table 9-1 on
page 9-3
Dewpoint Probe (for
Economization)
Dewpoint
See Table 9-1 on
page 9-3
Mixed Air Temp (ana-
log economizers only)
Temperature
See Table 9-1 on
page 9-3
Inputs
Sensor Type
Wiring
Instructions
Table 11-10
- Suction Group Inputs
Содержание E2
Страница 2: ......
Страница 4: ......
Страница 16: ......
Страница 24: ......
Страница 48: ......
Страница 55: ......
Страница 56: ......
Страница 72: ...6 16 E2 RX BX CX I O Manual 026 1614 Rev 4 5 JAN 2013 ...
Страница 75: ...BACnet The RS485 Network and Hardware Setup 6 19 ...
Страница 79: ...BACnet The RS485 Network and Hardware Setup 6 23 ...
Страница 80: ...6 24 E2 RX BX CX I O Manual 026 1614 Rev 4 5 JAN 2013 ...
Страница 81: ......
Страница 82: ......
Страница 92: ...8 6 E2 RX BX CX I O Manual 026 1614 Rev 4 5 JAN 2013 ...
Страница 94: ...8 8 E2 RX BX CX I O Manual 026 1614 Rev 4 5 JAN 2013 ...
Страница 114: ......
Страница 144: ......
Страница 203: ......
Страница 204: ......
Страница 226: ......
Страница 253: ......
Страница 254: ......
Страница 257: ......
Страница 258: ......
Страница 267: ......
Страница 268: ......
Страница 270: ......
Страница 282: ......