C6.1.11/0718-0619/E
57
Gas cooler alarms
Code
Name on
Visograph
Description
Cause
Action
Reset
PreHP Rec
PreHP Rec
High pressure on
CO
2
receiver pre-
alarm
GC28 > AIC98 (AIC99) > GC29
(Priority on probe failure
alarms)
The % of the valve updates
every second in order to reach
the correct percentage.
If the receiver pressure value
is between the values GC29
and GC28
– 1 (bar), the % of
valve opening is as follows:
Automatically
as soon as the HP REC
is active or as soon as AIC98 (AIC99) <
GC29
– GC30
HP REC
HP REC
High pressure on
CO
2
receiver
alarm
AIC98 (AIC99) > GC28
(Priority on probe failure
alarms)
The HPV will close (0%).
The BGV will open to a user-
defined % set by parameter
GC37.
Automatically
as soon as AIC98
(AIC99) < GC28
– GC30
LP REC
LP REC
Low pressure on
CO
2
receiver
alarm
AIC98 (AIC99) < GC31
The HPV will have a minimum
opening to a user-defined %
set by GC36.
If the PID % is greater than
GC36, then the PID % will be
the valve % output.
The BGV will close.
Automatically
as soon as AIC98
(AIC99) > GC31 + GC32
OA-XEV20D
OA-
XEV20D
XEV20D off-line
alarm
The XEV20D is used and loses
communication.
Only signalling
The communication is recovered
automatically
Table 23: Alarm code overview
Содержание Copeland EazyCool OME-4MTL-09X
Страница 1: ...Copeland Eazycool CO2 Refrigeration Units Application Guidelines ...
Страница 5: ......
Страница 16: ...C6 1 11 0718 0619 E 11 2 7 8 Exploded view of the CO2 unit Figure 12 Exploded view of the unit ...
Страница 67: ...62 C6 1 11 0718 0619 E Appendix 4 Ecodesign overview tables according to Regulation 2015 1095 EU ...
Страница 68: ...C6 1 11 0718 0619 E 63 ...