C6.1.11/0718-0619/E
23
2.9.14 How to reset the controller to factory settings
1)
Enter the "Service" menu
2)
Use the
UP
and
DOWN
keys to select the "Conf file management" sub-menu
3)
Press the
SET
key. The parameter map will be transferred from "Backup.conf" file to
"default_10D.conf" file.
Figure 30: Reset to factory settings
The controller will reboot, and the parameters will be reloaded from the "Param_model.conf" file.
2.9.15 How to save user
’s settings
NOTE: Saving the user
’s settings will overwrite the factory settings!
To update the back-up file with the current parameter map:
1)
Enter the "Service" menu
2)
Use the
UP
and
DOWN
keys to select the "Conf file management" sub-menu
3)
Press the
SET
key
4)
Use the
UP
and
DOWN
keys to select the "Send parameters to Backup.conf file" sub-menu
5)
Press the
SET
key
To load the parameters from the "Backup.conf" file to the iPro rack:
1)
Enter the "Load parameters from Backup.conf file" sub-menu
2)
Press the
SET
key. The parameters will be loaded from the "Backup.conf" file.
The iPro rack will reboot and the parameters will be reloaded to the "Conf file management" file.
2.9.16 Data logging
The controller will continuously store all the alarms in an endless loop
– maximum log file size 1MB.
There are 4 log files, of which only 3 can be exported:
▪
AccessLog
▪
AlarmLog
▪
ParamLog
▪
ParamAlarmLog
The ParamLog and ParamAlarmLog files contain the same variables, but:
▪
the ParamLog file has a fixed sampling rate (5 minutes);
▪
the ParamAlarmLog file stamps the info every time an alarm starts or stops.
Содержание Copeland EazyCool OME-4MTL-09X
Страница 1: ...Copeland Eazycool CO2 Refrigeration Units Application Guidelines ...
Страница 5: ......
Страница 16: ...C6 1 11 0718 0619 E 11 2 7 8 Exploded view of the CO2 unit Figure 12 Exploded view of the unit ...
Страница 67: ...62 C6 1 11 0718 0619 E Appendix 4 Ecodesign overview tables according to Regulation 2015 1095 EU ...
Страница 68: ...C6 1 11 0718 0619 E 63 ...