5.5.7 Two-Speed Timer Setup
The two-speed timers can be configured for the actuator to be controlled with
different opening and closing times. All configured timers are active in the LOCAL
and REMOTE modes.
NOTE:
All three timers, close, open, and anti-water hammer, can operate at the same time.
If two timer ranges overlap, the anti-water hammer timer overrides all timers.
1.
At the “
TWO-SPEED TIMER SETUP?
” prompt answer “
YES.
”
2.
Use the selector knob (
NEXT/BACK
) to review the settings for each timer.
3.
Use the control knob (
NO
) to select either
ON
or
OFF
, increment the
position percentage, and pulse time.
4.
Answer “
YES
” after each selection. See
Figure 5-12
.
Figure 5-12
Two-Speed Timer Setup
NO
NO
NO
NO
NO
Figure 5-12 Two-Spead Timer Setup
Go to
Figure 5-4
YES
YES
YES
YES
YES
Close Timer
<
On / Off
>
YES
Open Timer
<
On / Off
>
YES
YES
Anti-Water
Hammer
<
On / Off
>
YES
Timer Start
Position:
<
xx
>%
YES
YES
Timer Stop
Position:
<
xx
>%
YES
Pulse On Time:
<
xx.x
> Sec
Pulse Off Time:
<
xx.x
> Sec
TWO-SPEED
TIMER SETUP?
CLOSE
TIMER SETUP?
OPEN
TIMER SETUP?
ANTI-WATER
HAMMER SETUP?
Increment Position
1-99% in Steps of 1%
Increment Position
1-99% in Steps of 1%
1-10 sec in
0.5 sec Increments
1-100 sec in
1 sec Increments
NO
NO
NO
NO
YES
Timer Start
Position:
<
xx
>%
YES
YES
Timer Stop
Position:
<
xx
>%
YES
Pulse On Time:
<
xx.x
> Sec
Pulse Off Time:
<
xx.x
> Sec
Increment Position
1-99% in Steps of 1%
Increment Position
1-99% in Steps of 1%
1-10 sec in
0.5 sec Increments
1-100 sec in
1 sec Increments
NO
YES
Timer Start
Position:
<
xx
>%
YES
Pulse Off Time:
<
xx.x
> Sec
Increment Position
1-30% in Steps of 1%
NO
NO
NO
NO
YES
Pulse On Time:
<
xx.x
> Sec
1-10 sec in
0.5 sec Increments
1-100 sec in
1 sec Increments