Section 3: Installation
Installation
Figure 3-10 ACM Installation Connections - ACM
(Network Control Module)
Notes:
1.
All digital inputs have an input voltage range of 18-150 Vdc or 20-250 Vac.
2.
All digital relay outputs are rated for 5 A @ 30 Vdc or 5 A @ 250 Vac
Resistive, 2 A Inductive load.
3.
Jumpers can be added between Terminals 8 and 10, Terminals 32 and 34,
Terminals 36 and 38, and Terminals 40 and 42 but are not required.
4.
Emergency Stop requires jumper (between Terminals 20 and 22) or
normally closed contacts (actuator stops when contacts open).
5.
Remote display communication port is RS-485.
6.
If bare wires (without terminals) are connected, remove a maximum of
1/4 inch (6 mm) insulation.
Figure 3-11 ACM Wiring Connections
Emergency Stop (N.C.)
Remote Display Model Communication Port (+)
Emergency Stop (N.C.)
Remote Display Model Communication Port (-)
Earth Ground
1 3 5 7 9
11 13 15
17 19 21 23
2 4 6 8 10 12 14 16 18 20 22 24
26 28 30 32 34 36 38 40 42 44
25 27 29 31 33 35 37 39 41 43
}
}
}
}
}
}
}
(+)
(-)
Open
Close
Stop
Open Inhibit
Close Inhibit
ESD
Digital Input #1
Digital Input #2
Digital Input #3
Digital Input #4
Digital Input #5
Digital Input #6
Common (0V) for Control Inputs (1-3)
Common (0V) for Inhibit/ESD Inputs (4-6)
User Power Supply 24VDC Power Supply
Relay Output #1 Limit Switch Open (LSO)
Relay Output #2
Limit Switch Close (LSC)
Relay Output #3
Intermediate Limit A (LSA)
Relay Output #4
Intermediate Limit B (LSB)
Relay Output #5 Monitor Relay N.O.
Monitor Relay N.C.
AIN1+
AIN1-
AIN2+
AIN2-
Shield
Shield
AO1+
AO1-
AO2+
AO2-
Spare (n/c)
DCMlink (+)
Spare (n/c)
DCMlink (-)
Alternate
Function
Default
Function
Signal
ACM Option
All Analog I/O are Isolated,
Loop Powered
with Channel to Channel Isolation
ACM_CAM Option
}
(+)
(-)
(+)
(-)
Shield
Shield
Network Port A
Network Port B
CAM Option
}
ACM Wiring
Terminals
25 to 44