background image

7

 INSTALLER/CONFIGURATION MENU

1.  This control can be configured for:
 

MS2

 – Multi-Stage System (2 heat/2 cool)

 

HP1

 – Heat Pump with one stage of compressor (2 

heat/1 cool)

 

HP2

 – Heat Pump with two stage compressor or two

 

compressor system, Gas or Electric backup; (Dual Fuel

 

see screen reference number 33) (4 heat/2 cool)

 

SS1

 – Single Stage System (3 wire zone see wiring

 diagrams.
2. 

GAS or Electric (ELE)

 fan operation. If the heating 

system requires the thermostat to energize the fan, select 
ELE. Select GAS if the heating system energizes the 
fan on a call for heat. 

Note: Resetting the thermostat 

switches the option to GAS.

3. 

O/B Terminal selection

 – Selects the operation of the 

reversing valve (when item 1 is set to HP1 or HP2 only).  
 When set to "O" the changeover valve will be energized  
 in COOL to accommodate the majority of heat applica-
tions. If the heat pump requires the changeover valve to  
 energize in HEAT, select "B".

4. 

Programs per week 

– This control can be configured for 

7 independent day or 5+1+1 day programming or non-
programmable modes. Default is 7-day mode. The display 
indicates

 "7 Days"

 as default. Other options 

"5 Days"

 or 

"0 Days"

 can be selected. If 

"0 Days" 

is selected for non-

programmable mode, the step for EMR will be skipped, as 
this feature will not be available in this mode.

5. 

Program Steps per day

 –  Not available if configured for 

non-programmable. This control can be configured for 4 
or 2 program steps per day. Default is 

"4 PS" 

and can be 

toggled between 4 PS and 2 PS. 

6. 

System Switch Configuration (MS2/SS1) 

– This ther-

mostat is configured for Heat and Cool with Auto change-
over default (Cool-Off-Heat-Auto). It can be configured as 
Heat & Cool (Cool-Off-Heat), or Heat Only (Off-Heat), or 
Cool Only (Cool-Off).

 

When the control is in heat pump configuration 

(HP1/

 HP2)

, the system switch configuration will have an 

 

additional mode, 

Em

 for Emergency. 

7. 

Energy Management Recovery (EMR)

 – (this step is 

skipped if configured as non-programmable). When set 
to "On" causes the thermostat to start heating or cooling 
early to make the building temperature reach the program 
setpoint at the time you specify. 

 

Example:

 The heating program is 65°F at night and 70° 

at 7 AM. If the building temperature is 65°F, the difference 
is 5°F. Allowing 5 minutes per °F rise, the thermostat set-
point will change to 70° at 6:35 AM. Cooling allows more 
time per °F, because it takes longer to reach temperature.

8, 9 & 10. 

Cycle Rate Selection

 – The factory default setting  

is fast cycle (FA Cr) in all modes (Heat, Cool, Em). To 
change to slow cycling (SL, Cr), press touch keys   or 

 toggle between FA & SL. The cycle rates are below:

 

Mode 

   Med     Slow

 

Heat  

   0.6°F     1.5°F

 

Cool  

   1.2°F     1.7°F

 

Heat Pump     1.2°F     1.7°F

 

Emer Heat 

   0.6°F     1.7°F 

11. 

Select Compressor Lockout (CL)

 – Selecting (CL On) 

will cause the thermostat to wait 5 minutes between cool-
ing cycles. This is intended to help protect the compressor 
from short cycling. Some of the newer compressors have 

CONFIGURATION MENU

Screen

Reference

Number

SS1

MS2

HP1
HP2 

Press 

key

Displayed 

Factory 

(Default)

Press 

 or 

 

to select from 

listed options

Comments

Option

Selected

33

(35) dF

-5 - 50

Selects Dual Fuel setpoint (°F), dF selected On with outdoor sen-

sor available.

34

(05) dF

0 - 09

Selects Dual Fuel setpoint (°F), dF selected On with no outdoor 

sensor.

35

(60) Cd

0-99

Selects compressor off delay in seconds, dF selected On

36

(80) AO

-5 - 79

Selects Auxiliary Heat cut out temperature. This item appears 

if HP1 or HP2 is selected and outdoor sensor is installed and 

enabled.

37

(80) bP

79-20

Selects Blower balance point. Selection of 80 disables this feature. 

This item appears if HP1 or HP2 is selected and outdoor sensor is 

installed and enabled.

38

(OFF) Hd

On

Selects Humidity Display alternate with time.

39

Humidity 00

(Room Humidity)

-20 LO

20 HI

Selects Humidity Display adjustment.

40

(OFF) HR

LO, HI

Selects Auto Humidity reduction.

41

(OFF) AH

H, C, A

Selects Automatic Humidification.

42

(OFF) CH

On

Selects Cycle Humidifier.

43

OC (0)

od, OFF

Selects Optimum Comfort or Optimum Dehumidification or Off.

44

(OFF) Change 

UV Lamp

On

Selects Change UV Lamp feature. 

45

350 Days

25-1975

Change UV Lamp duration days.

46

(OFF) 

Change Pad

On

Selects Change Humidifier Pad feature.

47

100 Hrs

25-1975

Change Humidifier Pad duration hours.

48

OFF

Change Filter

On

Selects Change Filter feature.

49

200 Hrs

25-1975

Change Filter duration hours.

Содержание 1F95-1291

Страница 1: ...ury However this prod uct may replace a product that contains mercury Mercury and products containing mercury must not be discarded in household trash Do not touch any spilled mercury Wearing non absorbent gloves clean up any spilled mercury and place in a sealed container For proper disposal of a product containing mercury or a sealed container of spilled mercury place it in a suitable shipping c...

Страница 2: ...e Power Stealing Switches Fig 1 should be left in the On position for most systems The information in the following table details the thermostat power method and switch options WARNING Thermostat installation and all components of the control system shall conform to Class II circuits per the NEC code INSTALLATION Figure 1 Thermostat Base Multi Stage 1F95 1291 2 AA Batteries Power Stealing Switches...

Страница 3: ...ency Mode 1st stage Note Dual Fuel option de energizes Heat mode stage 1 compressor when auxiliary heat is energized Heat mode 3rd stage Emergency Mode 1st stage Note Dual Fuel option de energizes Heat mode stages 1 and 2 both compressors when auxiliary heat is energized Heat mode 4th stage Emergency Mode 2nd stage Note Dual Fuel option de energizes Heat mode stages 1 and 2 both compressors when a...

Страница 4: ...tem HOT NEUTRAL 120 VAC TRANSFORMER HM 24 VAC Humidifier System R Figure 7 Typical Wiring for 24V Humidifier System Dehumidification wiring without an electronically controlled variable speed blower system for single stage compressor system only HM DHM Humidification Terminal Energizes on call for heat if Humidity setpoint is above room humidity Can also be used to provide humidification independe...

Страница 5: ... 3 7 3 8 3 9 3 20 21 2 1 11 12 10 16 17 9 8 18 14 13 4 19 15 A steady Cool Savings display indicates the feature is enabled in the installer menu A flashing Cool Savings display indicates the feature is active 16 Remote indicates that the indoor remote temperature sensor is being accessed Outdoor Remote indi cates the outdoor remote temperature sensor is being accessed 17 Display time remote tempe...

Страница 6: ... available if 4 is 0 8 FA Heat Cr SL Selects Adjustable Anticipation cycle rate Heat 9 FA Cool Cr SL Selects Adjustable Anticipation cycle rate Cool 10 FA Cr AU Em SL Selects Adjustable Anticipation cycle rate auxiliary This item is only to appear if HP1 or HP2 is selected above 11 OFF CL On Selects Compressor Lockout 12 On dL OFF Selects Continuous Display backlight 13 0 Temperature 5 LO to 5 HI ...

Страница 7: ...h the program setpoint at the time you specify Example The heating program is 65 F at night and 70 at 7 AM If the building temperature is 65 F the difference is 5 F Allowing 5 minutes per F rise the thermostat set point will change to 70 at 6 35 AM Cooling allows more time per F because it takes longer to reach temperature 8 9 10 Cycle Rate Selection The factory default setting is fast cycle FA Cr...

Страница 8: ... to 6 When an offset starts or is active Cool Savings will flash on the display The principle of this energy saving feature takes advantage of the long air conditioning run times lowering the indoor humidity allowing a slightly higher temperature to feel comfortable As the peak load subsides this feature also takes advantage of the air conditioner s increased capacity under more efficient conditio...

Страница 9: ... stage separation This adjust ment allows a small change in the operation of your heat INSTALLER CONFIGURATION MENU pump system versus your auxiliary system relative to the thermostat adjustment The higher the number the sooner the auxiliary stage energizes for better comfort The lower the number the longer period of time before auxiliary is energized for more economy Note This setting is not minu...

Страница 10: ...ded maintenance schedule When Change UV Lamp is displayed you can clear it by pressing Clean Display 46 47 Change Humidifier Pad This feature allows the thermostat to display the words Change Pad after a set time of humidifier operation This is a reminder to main tain or clean your humidifier The factory set interval for Change Pad to be displayed is 100 hours of humidifier operation This should b...

Страница 11: ... and or property damage if the outdoor temperature is below 50 F DO NOT operate the cooling system CAUTION Fan On selection runs the fan continuously for increased air circulation or to allow additional air cleaning Tip Running the fan more frequently will increase your energy consumption Most systems use a 1 2 or 1 3 HP electric motor to power the fan Choose the System Setting Cool Off Heat Em Au...

Страница 12: ...u wish to copy to is flashing 5 Press Copy Copy will disappear the day you copied from will disappear and the day s you copied to will be on 6 If you wish to copy this same program into other days press Copy and repeat steps 3 4 and 5 7 Press Run Schedule to return to normal operation Fill in the blank schedule on the next page then Enter the Heating Program 1 Press the Menu key and then press Set...

Страница 13: ...of the week You can eliminate these two program periods in the configuration menu reference 5 if the building is occupied all day Day period will change to 6 00 AM and 70 and can be programmed as required Wake Up Morning Leave For Work Day Return Home Evening Go To Bed Night Heating Program 6 00 AM 70 F 8 00 AM 62 F 5 00 PM 70 F 10 00 PM 62 F Cooling Program 6 00 AM 75 F 8 00 AM 83 F 5 00 PM 75 F ...

Страница 14: ...n the terminal block allow connection of the remote sensor The thermostat must have 24 VAC Common connection to terminal C for the remote sensor to operate The remote sen sor can be enabled or disabled in the Installer Configuration menu item 29 When remote sensor Remote is selected Off factory de fault no remote sensor is enabled When remote sensor is selected On the next step is to select the re...

Страница 15: ... the dual fuel temperature setpoint menu item 33 can be set to a temperature of 5 through 50 When outdoor remote sensor is not installed a software logic based dual fuel number menu item 34 from 01 to 09 can be selected A higher temperature or dual fuel setting will provide a smaller stage separation between the heat pump and Aux to give more comfort A lower temperature or number will provide a la...

Страница 16: ... connection to verify they are not shorted or touching together No bare wire should stick out from under terminal block Try resetting the thermostat as de scribed above If the condition persists the manufacturer of your system or service person can instruct you on how to test the Heat Cool system for correct operation If the system operates correctly replace the thermostat Thermostat Setting Therm...

Отзывы: