background image

10

“HM”

 terminal) if the actual humidity is below the humid-

ity set point. The display indicates 

AH

. Pressing the   

key will cycle the display from 

OFF

 to 

(feature enabled 

in Heat mode) to 

C

 (feature enabled in Cool mode) to 

A

 

(feature enabled to Auto mode) and back to 

OFF

42. 

Cycle Humidifier (CH)

 – This feature provides an op-

tion that reduces the water usage by up to 50% when a 
flow-through humidifier is controlled by the thermostat. It 
is recommended for use on flow-through humidifiers only. 
The display indicates 

CH

 (

C

ycle 

H

umidifier) with the de-

fault indicating OFF. Pressing the   or   keys will toggle 
the display from 

OFF

 to 

On

 and back to 

OFF

. When CH is 

enabled, the humidifier will cycle to turn off for 10 minutes 
after it has run for 10 minutes. The blower and/or furnace 
will continue to run during the humidifier off period.

43. 

Programmable Dehumidification Optimal Comfort 

Mode (OC) or Optimal Dehumidification (Od)

 – This 

item can be selected to 

OC 

(Optimal Comfort mode), 

Od

 

(Optimal Dehumidification), or OFF. When Optimal Com-
fort 

(OC)

 is enabled, this feature automatically reduces 

indoor humidity with a call for 

Cooling

 if humidity is 2% 

above humidity setpoint. Humidity is set by pressing the 

Humidity

 key when in the appropriate mode, in this case 

Cooling

, and pressing the 

 or 

 keys to set desired 

humidity (range 40% to 95%) level followed by pressing 

Humidity

 key again. This dehumidification feature uses 

less energy by maintaining temperature and dehumidify-
ing only when a call for Cooling is required. Optimal De-
humidification 

(Od)

 when enabled, this feature automati-

cally reduces indoor humidity with a call for 

Cooling 

if 

humidity is 2% above setting. Humidity is set by pressing 
the 

HUMIDITY

 key when in the appropriate mode, in 

this case 

Cooling

, and pressing the 

 or 

keys to set 

desired humidity level followed by pressing 

Humidity 

key 

INSTALLER/CONFIGURATION MENU 

again. This dehumidification feature may use more energy 
by making dehumidification a priority initiating a call for 
cooling if humidity is 2% above desired setting. This 
feature may also over-cool the condition space by up to 3 
degrees to achieve the desired humidity level. (Note: Both 
dehumidification modes operate in Cooling mode only 
with a call for cooling)

44 & 45. 

Change UV Lamp

 – This feature allows the thermo-

stat to display the words 

"Change UV Lamp" 

(Call for 

Service of UV bulb) after a set time of UV bulb operation. 
This is a reminder to maintain your UV system at opti-
mum level of operation. When enabled, the factory set 
interval for 

"Change UV Lamp"

 to be displayed is 350 

days of UV bulb operation and can be adjusted in 25 day 
increments. This should be adjusted with respect to the 
bulb’s recommended maintenance schedule. 

 When 

"Change UV Lamp"

 is displayed, you can clear it 

by pressing Clean Display.

46 & 47. 

Change Humidifier Pad

 – This feature allows the 

thermostat to display the words 

"Change Pad"

 after a set 

time of humidifier operation. This is a reminder to main-
tain or clean your humidifier. The factory set interval for 

"Change

 

Pad"

 to be displayed is 100 hours of humidifier 

operation. This should be adjusted with respect to the 
humidifier’s recommended maintenance schedule.

 When 

"Change Pad"

 is displayed, you can clear it by 

pressing Clean Display.

48 & 49. 

Select Change Filter Run Time

 – This feature 

allows thermostat to display 

"Change Filter"

 after a set 

time of blower operation. This is a reminder to change 
or clean your air filter. This time can be set from 25 to 
1975 hours in 25 hour increments. A selection of OFF will 
cancel this feature. When 

"Change Filter" 

is displayed, 

you can clear it by pressing Clean Display. In a typical ap-
plication, 200 hours of run time is approximately 30 days.

OPERATING YOUR THERMOSTAT 

If at any time during testing your system does not operate 
properly, contact a qualified service person.

Fan Operation

If your system does not have a G terminal connection, skip to 

Heating System.

1.  Turn on power to system.
2. Press FAN key to 

ON

 position. The blower should begin     

to operate.

3. Press FAN key to 

AUTO

 position. The blower should  

stop immediately.

To prevent static discharge problems, touch side of 
thermostat to release static build-up before touching 
any keys.

NOTE

Check Thermostat Operation

Do not allow the compressor to run unless the compres-
sor oil heaters have been operational for 6 hours and the 
system has not been operational for at least 5 minutes.

CAUTION

!

Heating/Humidifier

1.  Press SYSTEM key to select HEAT. If the auxiliary heating 

system has a standing pilot, be sure to light it.

2. Press   to adjust thermostat setting to 1°

 

above the 

room temperature. The heat pump system should begin to 
operate. The display should show "

System On"

. How-

ever, if the system configuration is set to HP1 or HP2 
and setpoint temperature display is flashing, the 5 minute 
compressor lockout feature is operating (see Configura-
tion menu, item 11).

3.  Adjust temperature setting to 3° above room temperature. 

If your system configuration is set at MS2, HP1 or HP2, 
the auxiliary heat system should begin to operate and the 
display will show 

"System On +2"

.

4. Press   to adjust the thermostat below room tempera-

ture. The heating system should stop operating.

To check the humidifier when 

System On

 appears and the 

heating system is running press the 

HUMIDITY*

 button once. 

Press 

 to adjust the humidity 2% or more above the room 

humidity level setpoint range. (Humidity setpoint can be 
adjusted from 5 to 50%.) 

Hum On

 will appear indicating it is 

calling for the humidifier. 

*Note: 

If 

Auto Schedule

 is displayed instead of 

Humidity

Auto Schedule

 must be turned off in the Configuration Menu.

Содержание 1F95-1291

Страница 1: ...ury However this prod uct may replace a product that contains mercury Mercury and products containing mercury must not be discarded in household trash Do not touch any spilled mercury Wearing non absorbent gloves clean up any spilled mercury and place in a sealed container For proper disposal of a product containing mercury or a sealed container of spilled mercury place it in a suitable shipping c...

Страница 2: ...e Power Stealing Switches Fig 1 should be left in the On position for most systems The information in the following table details the thermostat power method and switch options WARNING Thermostat installation and all components of the control system shall conform to Class II circuits per the NEC code INSTALLATION Figure 1 Thermostat Base Multi Stage 1F95 1291 2 AA Batteries Power Stealing Switches...

Страница 3: ...ency Mode 1st stage Note Dual Fuel option de energizes Heat mode stage 1 compressor when auxiliary heat is energized Heat mode 3rd stage Emergency Mode 1st stage Note Dual Fuel option de energizes Heat mode stages 1 and 2 both compressors when auxiliary heat is energized Heat mode 4th stage Emergency Mode 2nd stage Note Dual Fuel option de energizes Heat mode stages 1 and 2 both compressors when a...

Страница 4: ...tem HOT NEUTRAL 120 VAC TRANSFORMER HM 24 VAC Humidifier System R Figure 7 Typical Wiring for 24V Humidifier System Dehumidification wiring without an electronically controlled variable speed blower system for single stage compressor system only HM DHM Humidification Terminal Energizes on call for heat if Humidity setpoint is above room humidity Can also be used to provide humidification independe...

Страница 5: ... 3 7 3 8 3 9 3 20 21 2 1 11 12 10 16 17 9 8 18 14 13 4 19 15 A steady Cool Savings display indicates the feature is enabled in the installer menu A flashing Cool Savings display indicates the feature is active 16 Remote indicates that the indoor remote temperature sensor is being accessed Outdoor Remote indi cates the outdoor remote temperature sensor is being accessed 17 Display time remote tempe...

Страница 6: ... available if 4 is 0 8 FA Heat Cr SL Selects Adjustable Anticipation cycle rate Heat 9 FA Cool Cr SL Selects Adjustable Anticipation cycle rate Cool 10 FA Cr AU Em SL Selects Adjustable Anticipation cycle rate auxiliary This item is only to appear if HP1 or HP2 is selected above 11 OFF CL On Selects Compressor Lockout 12 On dL OFF Selects Continuous Display backlight 13 0 Temperature 5 LO to 5 HI ...

Страница 7: ...h the program setpoint at the time you specify Example The heating program is 65 F at night and 70 at 7 AM If the building temperature is 65 F the difference is 5 F Allowing 5 minutes per F rise the thermostat set point will change to 70 at 6 35 AM Cooling allows more time per F because it takes longer to reach temperature 8 9 10 Cycle Rate Selection The factory default setting is fast cycle FA Cr...

Страница 8: ... to 6 When an offset starts or is active Cool Savings will flash on the display The principle of this energy saving feature takes advantage of the long air conditioning run times lowering the indoor humidity allowing a slightly higher temperature to feel comfortable As the peak load subsides this feature also takes advantage of the air conditioner s increased capacity under more efficient conditio...

Страница 9: ... stage separation This adjust ment allows a small change in the operation of your heat INSTALLER CONFIGURATION MENU pump system versus your auxiliary system relative to the thermostat adjustment The higher the number the sooner the auxiliary stage energizes for better comfort The lower the number the longer period of time before auxiliary is energized for more economy Note This setting is not minu...

Страница 10: ...ded maintenance schedule When Change UV Lamp is displayed you can clear it by pressing Clean Display 46 47 Change Humidifier Pad This feature allows the thermostat to display the words Change Pad after a set time of humidifier operation This is a reminder to main tain or clean your humidifier The factory set interval for Change Pad to be displayed is 100 hours of humidifier operation This should b...

Страница 11: ... and or property damage if the outdoor temperature is below 50 F DO NOT operate the cooling system CAUTION Fan On selection runs the fan continuously for increased air circulation or to allow additional air cleaning Tip Running the fan more frequently will increase your energy consumption Most systems use a 1 2 or 1 3 HP electric motor to power the fan Choose the System Setting Cool Off Heat Em Au...

Страница 12: ...u wish to copy to is flashing 5 Press Copy Copy will disappear the day you copied from will disappear and the day s you copied to will be on 6 If you wish to copy this same program into other days press Copy and repeat steps 3 4 and 5 7 Press Run Schedule to return to normal operation Fill in the blank schedule on the next page then Enter the Heating Program 1 Press the Menu key and then press Set...

Страница 13: ...of the week You can eliminate these two program periods in the configuration menu reference 5 if the building is occupied all day Day period will change to 6 00 AM and 70 and can be programmed as required Wake Up Morning Leave For Work Day Return Home Evening Go To Bed Night Heating Program 6 00 AM 70 F 8 00 AM 62 F 5 00 PM 70 F 10 00 PM 62 F Cooling Program 6 00 AM 75 F 8 00 AM 83 F 5 00 PM 75 F ...

Страница 14: ...n the terminal block allow connection of the remote sensor The thermostat must have 24 VAC Common connection to terminal C for the remote sensor to operate The remote sen sor can be enabled or disabled in the Installer Configuration menu item 29 When remote sensor Remote is selected Off factory de fault no remote sensor is enabled When remote sensor is selected On the next step is to select the re...

Страница 15: ... the dual fuel temperature setpoint menu item 33 can be set to a temperature of 5 through 50 When outdoor remote sensor is not installed a software logic based dual fuel number menu item 34 from 01 to 09 can be selected A higher temperature or dual fuel setting will provide a smaller stage separation between the heat pump and Aux to give more comfort A lower temperature or number will provide a la...

Страница 16: ... connection to verify they are not shorted or touching together No bare wire should stick out from under terminal block Try resetting the thermostat as de scribed above If the condition persists the manufacturer of your system or service person can instruct you on how to test the Heat Cool system for correct operation If the system operates correctly replace the thermostat Thermostat Setting Therm...

Отзывы: