background image

15

 

 PROGRAMMING

 

 TROUBLESHOOTING

Averaging or Weighting Remote Sensors

The thermostat will weight or average the temperature of the 
indoor remote sensor with the local sensor in the thermostat 
for each program period. The averaging will be active only 
when the local sensor and the indoor remote sensor are both 
functional and enabled in the Installer/Configuration menu.
When the thermostat is in the Set Schedule mode, the weight 
of the indoor sensor will be shown in the current temperature 
digits of the display. The weight will show as 

A2

 (average and 

default), 

H4

 (high) or 

L1

 (low). Pressing the   and   keys at 

the same time will change the weight for the program period. 
The weight of the thermostat sensor is fixed. 
In normal operation of the thermostat, the current tempera-
ture displayed will be the weighted average of the local 
sensor and the remote sensor using the formula (local sensor 
weight x local sensor temperature) + (remote sensor weight x 
remote sensor temperature) / (local sensor remote 
sensor weight).
Example: Local sensor temperature is 80° and the remote 
sensor is 70°. 
If weight is selected 

H4

, the averaged temperature of 72° will 

be displayed.
(1 x 80) + (4 x 70) / 5 = 72° 
If weight is selected 

A2

, the average temperature of 73° will 

be displayed.
(1 x 80) + (2 x 70) / 3 = 73.3°
If weight is selected

 L1

, the average temperature of 75° will 

be displayed.
(1 x 80) + (1 x 70) / 2 = 75°
The example shows that the weight selected would prioritize 
the overall averaged temperature between the two sensors. 
The high weight selection caused the remote sensor to have 
a higher influence in the calculated temperature average than 
the local sensor and the low weight selection caused the 
remote sensor to have less influence. 

Dual Fuel Temperature Setpoint

When the thermostat is configured for Heat Pump mode and 
the Dual Fuel feature is selected on, the thermostat can moni-
tor the outside temperature using remote sensor F145-1378 
or use software logic to determine when to switch to gas heat 
and shut down the compressor. This eliminates the need for a 
fossil fuel kit. 
The user selectable temperature is called the dual fuel tem-
perature setpoint, 

dF

 and is set in the Installer/Configuration 

menu, items 33 or 34. With outdoor remote sensor installed 
and enabled, the dual fuel temperature setpoint (menu item 
33) can be set to a temperature of -5° through 50°. When 
outdoor remote sensor is not installed, a software logic 
based dual fuel number (menu item 34) from 01 to 09 can be 
selected. A higher temperature or dual fuel setting will provide 
a smaller stage separation between the heat pump and Aux 
to give more comfort. A lower temperature or number will 
provide a larger stage separation for more economy.
After the dual fuel temperature setpoint is set and 

 is 

pressed, a delay, 

Cd

, can be set for compressor shutdown 

after the auxiliary stage is energized. This delay can be set 
from 0 seconds to 99 seconds to minimize the time that the 
system may blow cooler air until the alternate source of heat 
comes on. Default setting for delay is 60. When setting the 
delay, if the   or   keys are held depressed, the setpoint 
will increase or decrease at the rate of one degree every half 
second for the first three seconds and double the speed after 
three seconds.

Blower Balance Point for Heating

Requires DHM connection from thermostat to heat pump 
system. Air to air heat pumps use a fast fan speed to circu-
late warm air for first stage heating. As outdoor temperatures 
drop, the heat pump produces less heat and a high fan speed 
makes the air from the ducts feel cooler. Blower Balance Point 
allows you to select an outdoor temperature to slow the fan 
speed so the air from the duct feels warmer. Select an out-
door temperature where the air from the ducts starts to feel 
cool (Installer Configuration Menu item 37). When the outdoor 
temperature drops to the selected temperature, the thermo-
stat will slow the fan speed so the outlet air feels warmer.

Comfort Alert Codes

The Comfort Alert diagnostics product monitors the air con-
ditioning outdoor systems with single phase Copeland Scroll 
compressors. Abnormal system and electrical conditions are 
indicated by flashing ALERT codes on the yellow LED on the 
Comfort Alert module. The flash codes are transmitted to the 
thermostat by the Comfort Alert Thermostat interface module. 
The Comfort Alert compatible thermostat displays 

“Call For 

Service” 

that flashes at the same rate as the yellow LED on 

the Comfort Alert module. 

Comfort Alert Codes

1 Flash

Long run time

2 Flashs

System pressure trip

3 Flashs

Short cycling

4 Flashs

Locked rotor

5 Flashs

Open circuit

6 Flashs

Open start circuit

7 Flashs

Open run circuit

8 Flashs

Welded Contactor

9 Flashs

Low voltage

Содержание 1F95-1291

Страница 1: ...ury However this prod uct may replace a product that contains mercury Mercury and products containing mercury must not be discarded in household trash Do not touch any spilled mercury Wearing non absorbent gloves clean up any spilled mercury and place in a sealed container For proper disposal of a product containing mercury or a sealed container of spilled mercury place it in a suitable shipping c...

Страница 2: ...e Power Stealing Switches Fig 1 should be left in the On position for most systems The information in the following table details the thermostat power method and switch options WARNING Thermostat installation and all components of the control system shall conform to Class II circuits per the NEC code INSTALLATION Figure 1 Thermostat Base Multi Stage 1F95 1291 2 AA Batteries Power Stealing Switches...

Страница 3: ...ency Mode 1st stage Note Dual Fuel option de energizes Heat mode stage 1 compressor when auxiliary heat is energized Heat mode 3rd stage Emergency Mode 1st stage Note Dual Fuel option de energizes Heat mode stages 1 and 2 both compressors when auxiliary heat is energized Heat mode 4th stage Emergency Mode 2nd stage Note Dual Fuel option de energizes Heat mode stages 1 and 2 both compressors when a...

Страница 4: ...tem HOT NEUTRAL 120 VAC TRANSFORMER HM 24 VAC Humidifier System R Figure 7 Typical Wiring for 24V Humidifier System Dehumidification wiring without an electronically controlled variable speed blower system for single stage compressor system only HM DHM Humidification Terminal Energizes on call for heat if Humidity setpoint is above room humidity Can also be used to provide humidification independe...

Страница 5: ... 3 7 3 8 3 9 3 20 21 2 1 11 12 10 16 17 9 8 18 14 13 4 19 15 A steady Cool Savings display indicates the feature is enabled in the installer menu A flashing Cool Savings display indicates the feature is active 16 Remote indicates that the indoor remote temperature sensor is being accessed Outdoor Remote indi cates the outdoor remote temperature sensor is being accessed 17 Display time remote tempe...

Страница 6: ... available if 4 is 0 8 FA Heat Cr SL Selects Adjustable Anticipation cycle rate Heat 9 FA Cool Cr SL Selects Adjustable Anticipation cycle rate Cool 10 FA Cr AU Em SL Selects Adjustable Anticipation cycle rate auxiliary This item is only to appear if HP1 or HP2 is selected above 11 OFF CL On Selects Compressor Lockout 12 On dL OFF Selects Continuous Display backlight 13 0 Temperature 5 LO to 5 HI ...

Страница 7: ...h the program setpoint at the time you specify Example The heating program is 65 F at night and 70 at 7 AM If the building temperature is 65 F the difference is 5 F Allowing 5 minutes per F rise the thermostat set point will change to 70 at 6 35 AM Cooling allows more time per F because it takes longer to reach temperature 8 9 10 Cycle Rate Selection The factory default setting is fast cycle FA Cr...

Страница 8: ... to 6 When an offset starts or is active Cool Savings will flash on the display The principle of this energy saving feature takes advantage of the long air conditioning run times lowering the indoor humidity allowing a slightly higher temperature to feel comfortable As the peak load subsides this feature also takes advantage of the air conditioner s increased capacity under more efficient conditio...

Страница 9: ... stage separation This adjust ment allows a small change in the operation of your heat INSTALLER CONFIGURATION MENU pump system versus your auxiliary system relative to the thermostat adjustment The higher the number the sooner the auxiliary stage energizes for better comfort The lower the number the longer period of time before auxiliary is energized for more economy Note This setting is not minu...

Страница 10: ...ded maintenance schedule When Change UV Lamp is displayed you can clear it by pressing Clean Display 46 47 Change Humidifier Pad This feature allows the thermostat to display the words Change Pad after a set time of humidifier operation This is a reminder to main tain or clean your humidifier The factory set interval for Change Pad to be displayed is 100 hours of humidifier operation This should b...

Страница 11: ... and or property damage if the outdoor temperature is below 50 F DO NOT operate the cooling system CAUTION Fan On selection runs the fan continuously for increased air circulation or to allow additional air cleaning Tip Running the fan more frequently will increase your energy consumption Most systems use a 1 2 or 1 3 HP electric motor to power the fan Choose the System Setting Cool Off Heat Em Au...

Страница 12: ...u wish to copy to is flashing 5 Press Copy Copy will disappear the day you copied from will disappear and the day s you copied to will be on 6 If you wish to copy this same program into other days press Copy and repeat steps 3 4 and 5 7 Press Run Schedule to return to normal operation Fill in the blank schedule on the next page then Enter the Heating Program 1 Press the Menu key and then press Set...

Страница 13: ...of the week You can eliminate these two program periods in the configuration menu reference 5 if the building is occupied all day Day period will change to 6 00 AM and 70 and can be programmed as required Wake Up Morning Leave For Work Day Return Home Evening Go To Bed Night Heating Program 6 00 AM 70 F 8 00 AM 62 F 5 00 PM 70 F 10 00 PM 62 F Cooling Program 6 00 AM 75 F 8 00 AM 83 F 5 00 PM 75 F ...

Страница 14: ...n the terminal block allow connection of the remote sensor The thermostat must have 24 VAC Common connection to terminal C for the remote sensor to operate The remote sen sor can be enabled or disabled in the Installer Configuration menu item 29 When remote sensor Remote is selected Off factory de fault no remote sensor is enabled When remote sensor is selected On the next step is to select the re...

Страница 15: ... the dual fuel temperature setpoint menu item 33 can be set to a temperature of 5 through 50 When outdoor remote sensor is not installed a software logic based dual fuel number menu item 34 from 01 to 09 can be selected A higher temperature or dual fuel setting will provide a smaller stage separation between the heat pump and Aux to give more comfort A lower temperature or number will provide a la...

Страница 16: ... connection to verify they are not shorted or touching together No bare wire should stick out from under terminal block Try resetting the thermostat as de scribed above If the condition persists the manufacturer of your system or service person can instruct you on how to test the Heat Cool system for correct operation If the system operates correctly replace the thermostat Thermostat Setting Therm...

Отзывы: